This page intentionally left blank. Argus Technologies Ltd. Burnaby, British Columbia. Telephone: 604 436 5900 Fax: 604 436 1233 Argus Technologies reserves the right to make changes to the products and information contained in this document without notice. Copyright 2008 Argus Technologies Ltd. Argus® is a registered trademark of Argus Technologies Ltd. All Rights Reserved. Printed in Canada. Visit www.argus.
Te17 Outdoor Enclosure 030-729-B2 The following documents and drawings are included in this manual to provide the necessary information required for installation of the product: • Important Safety Instructions • Specifications: 030-729-B1 Rev A • Installation Instructions: 030-729-C0 Rev A • Outline Drawing: 030-729-06 • Warranty Policy: 048-507-10 • Factory Service Information: 048-527-10 Argus Technologies Ltd. Printed in Canada. © 2005 Argus Technologies Ltd.
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This section contains important instructions that should be followed during the installation and maintenance of equipment and batteries. Please read all of the instructions before operating the equipment, and save this manual for future reference. A licensed electrician MUST perform all AC service power connections.
Electrical Safety WARNING Hazardous voltages are present at the input of a power system. The DC output from rectifiers and batteries, though not dangerous in voltage, has a high short-circuit current capacity that may cause severe burns and electrical arcing. Before working with any live battery or power system, the following precautions should be followed: • • • Remove all metallic jewelry; e.g., watches, rings, eyeglasses, necklaces. Safety glasses with side shields must be worn at all times.
Enclosure Support A supporting structure (slab, roof top, etc. with a minimum loading capacity of 600lb./sq.ft.) is required to support a fully loaded enclosure (rectifiers, batteries, air conditioning, etc.). Concrete Slab Cast-in-place or pre-cast concrete slabs can be used. Place the enclosure on the concrete slab and secure with 'Hilti' HSL heavy-duty expansion anchor bolts or approved equivalent.
SPECIFICATIONS FOR ARGUS TECHNOLOGIES’ OUTDOOR ENCLOSURE TE17 Electrical Input Voltage: 120/240Vac, 3-wire + PE, 60Hz single phase Input Current: 80A maximum Output Voltage: 42-60Vdc (48V nominal) Output Power, DC: 3kW maximum Output Power, AC (convenience outlets): 120Vac, 45A maximum, 60Hz Recommended Feeder Breaker: 100A Mechanical Enclosure Dimensions: 1473mm H x 762mm W x 711mm D (58” H x 30” W x 28” D) Weight: 204 kg (450 lb.) [weight is approx.
This page intentionally left blank.
TE17 OUTDOOR ENCLOSURE INSTALLATION 030-729-C0
NOTE: The information contained in this manual is preliminary and is subject to change without notice. NOTE: Images contained in this document are for illustrative purposes only and may not exactly match your installation. NOTE: Review the drawings and illustrations contained in the documentation package provided before proceeding. If there are questions regarding the safe installation of this equipment, please contact Argus Technologies or the nearest Argus representative.
ARGUS TECHNOLOGIES TE17 OUTDOOR ENCLOSURE INSTALLATION TABLE OF CONTENTS SECTION PAGE 1 TE17 OVERVIEW ..........................................................................................................................1 2 TRANSPORTATION AND STORAGE .................................................................................................2 2.1 2.2 2.3 2.4 3 SITE CONSIDERATIONS................................................................................................................
TE17 OUTDOOR ENCLOSURE INSTALLATION ARGUS TECHNOLOGIES This page intentionally left blank.
ARGUS TECHNOLOGIES 1 TE17 OUTDOOR ENCLOSURE INSTALLATION TE17 OVERVIEW The Argus Tempest® Te17 provides a modular enclosure solution. It is configured for a wide range of outdoor power applications and can be configured as a stand-alone single bay, or expanded to two or more enclosures. These instructions detail the Te17 as used as an outdoor modular wireless equipment enclosure. Figure 1–Outline illustrations of Te17 Note: See outline drawings included with this documentation package.
TE17 OUTDOOR ENCLOSURE INSTALLATION 2 TRANSPORTATION AND STORAGE 2.1 Packaging ARGUS TECHNOLOGIES The Te17 Outdoor Enclosure and components are shipped on individual pallets and shrink wrapped. The pallet is approximately 1.22m x 1.22m (4’ by 4’) and the overall height including pallet and enclosure is approximately 1.65m (65”). The enclosures and components cannot be stacked.
ARGUS TECHNOLOGIES 3 TE17 OUTDOOR ENCLOSURE INSTALLATION SITE CONSIDERATIONS The information in this section is intended as a guideline only; there may be sitespecific requirements and other factors that will require individual attention, such as jurisdictional codes and construction covenants. 3.1 Site Selection The Te17 has been designed as an outdoor power equipment enclosure.
TE17 OUTDOOR ENCLOSURE INSTALLATION 3.2 ARGUS TECHNOLOGIES Enclosure Support A supporting structure (slab, roof top, etc. with a minimum loading capacity of 600lb./sq.ft.) is required to support a fully loaded enclosure (rectifiers, batteries, air conditioning, etc.). 3.2.1 Concrete Slab Cast-in-place or pre-cast concrete slabs can be used. Place the enclosure on the concrete slab and secure with 'Hilti' HSL heavy-duty expansion anchor bolts or approved equivalent.
ARGUS TECHNOLOGIES TE17 OUTDOOR ENCLOSURE INSTALLATION 4 ENCLOSURE INSTALLATION 4.1 Enclosure Preparation Remove the protective covering from the system. The doors may be opened with a socket pin-head key, Argus #647-060-10. (images not to scale) Figure 4–Illustration of door latch and socket pin-head key for Te17 panels The door panels are designed to be locked with a pad-lock and are secured for shipping using tie-wraps. Cut these away and open all doors.
TE17 OUTDOOR ENCLOSURE INSTALLATION 4.2 ARGUS TECHNOLOGIES Enclosure Disassembly Some disassembly of the Te17 is possible for locations with limited access; e.g., narrow corridor. The enclosure air conditioner and riser may be removed as follows: 1b Figure 6–Ground cable connection to riser: 1. Detach ground cable [a] from riser and push cable through access boot [b] to the enclosure section above. 1a Figure 7–Intrusion alarm connection from riser: 2.
ARGUS TECHNOLOGIES 4.3 TE17 OUTDOOR ENCLOSURE INSTALLATION Lifting Preparation CAUTION All local safety practices and guidelines must be followed while lifting the enclosure. Do not lift enclosure with batteries installed. All personnel involved with lifting and placing the enclosure should wear head and eye protection and gloves when required. Crane Operation Only properly trained and certified personnel should operate the crane.
TE17 OUTDOOR ENCLOSURE INSTALLATION 5 ARGUS TECHNOLOGIES GROUNDING DANGER An enclosure that is not properly grounded can present an electrical hazard. A proper grounding system that meets or exceeds the specifications of the equipment must be designed and installed prior to or in conjunction with the construction of the mounting scenario.
ARGUS TECHNOLOGIES 6 TE17 OUTDOOR ENCLOSURE INSTALLATION POWER SYSTEM INSTALLATION AND CONNECTION This section is provided for qualified personnel to install and interconnect the power components within the Argus Outdoor Enclosure. For battery installation refer primarily to the manufacturer’s guidelines for more specific information. 6.1 Tools Required Various tools are essential for DC power system installation.
TE17 OUTDOOR ENCLOSURE INSTALLATION 6.2 ARGUS TECHNOLOGIES Utility Connection Verify electrical codes prior to installation. Codes may vary and contain specific conduit and wire sizes for connection to the AC load center. Connection to utility power must be approved by the local utility before installing the power supply. AC power is brought in through a load center located on the left front side of the enclosure. Procedure: 1. Locate the AC load center on the inside of the enclosure.
ARGUS TECHNOLOGIES 6.3 TE17 OUTDOOR ENCLOSURE INSTALLATION Battery Installation WARNING Review the safety instructions provided at the beginning of this manual. Follow battery manufacturer’s safety recommendations when working around battery systems. 6.3.1 Preparation/Mounting The Te17 must be mounted before installation of the bottom tray of batteries may be completed. Batteries should be located in a temperature-controlled environment; i.e., Tempest. The temperature should be regulated at approx.
TE17 OUTDOOR ENCLOSURE INSTALLATION ARGUS TECHNOLOGIES Company: ________________________________________________________Date: _____________________ Address:____________________________________________________________________________________ Battery location and/or number: _________________________________________________________________ No.
ARGUS TECHNOLOGIES 6.4 TE17 OUTDOOR ENCLOSURE INSTALLATION Alarm Terminations Refer to the documentation package that comes with your power system components. All Tempest system alarms are connected via a punchdown “66 block” from the local alarm-sending unit. A system controller can provide a central point for all external alarm lead connections – alarm table to be provided. The type of alarm input required by the alarm sending unit determines how the alarm contacts are configured and wired; i.e.
TE17 OUTDOOR ENCLOSURE INSTALLATION 7 TEST AND COMMISSIONING (OVERVIEW) 7.1 System ARGUS TECHNOLOGIES All Argus power system components undergo thorough factory testing. All levels/alarms are set to predetermined values as detailed in their individual component manuals except where custom levels are specified. Good installation practice is to check the operation of all features and alarms and to set the power system levels in accordance with the specific requirements of your system.
This page intentionally left blank.
5(9,6,216 /75 3 % 237,21$/ 0(7(5 62&.(7 $1' ',6&211(&7 0(7(5 127 6+2:1 $ '(6&5,37,21 '$7( $33' 237,21$/ 127(6 $''(' - 8 : 6 83'$7(' 3$576 6': 0( 5(9 %< 237,21$/ /,)7,1* %5$&.(76 $& 32:(5 (175$1&( :+(1 0(7(5 62&.
87,/,7< 0(7(5 723 9,(: 23(1 '225 723 9,(: &/26(' '225 7+(6( '(6,*16 $1' 63(&,),&$7,216 $5( 7+( 3523(57< 2) $5*86 7(&+12/2*,(6 $1' 6+$// 127 %( &23,(' 25 86(' )25 0$18)$&785,1* :,7+287 ,76 :5,77(1 &216(17 6&$/( 1 7 6 7,7/( 287/,1( '5$:,1* 7H (1&/2685( F $5*86 7(&+12/2*,(6 2 ,668( '$7( 6,=( 7<3( ':* 12 ',0(16,216 $5( ,1 ,1&+(6 % ' 6+((7 2) 5(9 $
&/ '(7$,/ $ 6&$/( 5,*+7 6,'( &/ 7+(6( '(6,*16 $1' 63(&,),&$7,216 $5( 7+( 3523(57< 2) $5*86 7(&+12/2*,(6 $1' 6+$// 127 %( &23,(' 25 86(' )25 0$18)$&785,1* :,7+287 ,76 :5,77(1 &216(17 )5217 6&$/( 1 7 6 7,7/( 287/,1( '5$:,1* 7H (1&/2685( F $5*86 7(&+12/2*,(6 2 ,668( '$7( 6,=( 7<3( ':* 12 ',0(16,216 $5( ,1 ,1&+(6 % ' 6+((7 2) 5(9 $
WARRANTY AND SERVICE INFORMATION Technical Support Technical support staff are available for answering general questions related to installation, operation and maintenance of Argus products. In Canada and the USA, call Argus toll free at +1-888-GO-ARGUS (+1-888-462-7487) 7:30 am to 5:00 pm Pacific Standard Time. For emergencies, call +1-888-GO-ARGUS (+1-888-462-7487) 24 hours a day, seven days a week. Customers outside Canada and the USA, call +1-604-436-5547 for technical support.
Service Centers Factory Service Centers Canada and International Argus Technologies Ltd. ATTN: RMA Returns 7033 Antrim Avenue Burnaby, BC, V5J 4M5 Canada Tel: +1 604 436 5900 Fax: +1 604 436 1233 Email: returns@argusdcpower.com USA Argus Technologies Inc. ATTN: RMA Returns 3116 Mercer Avenue Bellingham, WA, 98225 USA Tel: +1-360 756 4904 Fax: +1-360 647 0498 Email: returns-usa@argusdcpower.com Asia-Pacific PCM Electronics (Dong Guan) Co., Ltd.