Manual
2. Specifications
22
018-041-C0-003 Rev. C
2.1 Channel Parameters
Table 2-1 Channel Parameters
Hi State Lo State
Channel
Description
Parameter name Units Maj Low Min Low Min Hi Maj Hi Note
Analog Inputs Internal Temperature (C) 0 10 50 60
Analog Inputs
External
Temperature
(C) 0 10 50 60 3
Analog Inputs AC Output Current 1 (AMPS) 0.5 2 25 25.5
Analog Inputs AC Output Current 2 (AMPS) 0.5 2 25 25.5
Analog Inputs Battery Voltage #1 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #2 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #3 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #4 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #5 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #6 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #7 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #8 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #9 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #10 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #11 (VDC) 10 11 14.4 14.8
Analog Inputs Battery Voltage #12 (VDC) 10 11 14.4 14.8
Analog Inputs AC Output Voltage (VAC) 50 55 95 98
Analog Inputs AC Input Voltage (VAC) 95 100 125 128 2
Digital input Standby Mode Normal Standby
Digital input Tamper Switch Open Closed
Digital input Output Fail Alarm Normal Alarm
Digital input General Alarm Normal Alarm 1
Digital input APU Test Fail Alarm Normal 1
Digital input Engine Status OFF ON 1
Digital input APU Fail / ECM Alarm Normal 1
Digital input APU Response Alarm Normal 1
Digital input Gas Hazard Alarm Alarm Normal 1
Digital input APU Engine Alarm Alarm Normal 1
Digital input Generator Enclosure Open Closed 1
Digital input Generator Tamper Closed Open 1
Digital output Standby ON / OFF OFF ON
Digital output Equalize ON / OFF OFF ON
Digital output Engine ON / OFF OFF ON
Note 1 - Generator
Note 2 - AC Input 120 VAC Models
Note 3 - External Temperature
Analog Inputs AC Input Voltage (VAC) 200 210 245 255 4
Analog Inputs Generator Battery (VDC) 10 11 14.4 14.8
Note 4 - AC Input 240 VAC Models