Chapter 5 Parameter Introductions
P0.03 Frequency setting selection
Range: 0~5【0】
0: Frequency setting 1
1: Terminal Selection
2: Frequency setting 1+ Frequency setting 2
3: | Frequency setting 1- Frequency setting 2 |
4: Min(Frequency setting 1, Frequency setting 2)
5: Max(Frequency setting 1, Frequency setting 2)
Note:
◆Frequency settings 1: Frequency set by P0.01 (Frequency setting 1).
◆Terminal Selection: If defined the "FC" function terminals (see P3.01 ~ P3.08), and
the terminal function is effective, P0.02 (frequency setting 2) will be selected as the
final frequency setting ; if defined this function terminal but the terminal function is
not effective, P0.01 (frequency setting 1) will be selected. If undefined the "FC"
function terminal, P0.01 (frequency setting 1) will be the default frequency setting .
Frequency setting selection can be switched between the two different signals.
◆Settings 2 to 5: The final reference frequency value will be decided by frequency
setting 1 and frequency setting 2 after the corresponding arithmetic.
Exceptions:
If P0.01 is set to 7 (UP / DOWN) or 10 (wobble frequency operating), Setting value 3
to 5 of P0.03 (P0.03=3~5) will be invalid, and setting value 0 will be valid. See
terminal UP / DOWN function definition in parameter group P3 and wobble frequency
operating definition in parameter group P6 for details.
If P0.01 is set to 9 (PID), the analog PID amplitude will be defined by P2.11, when
P0.03 is set to 3 to 5 (P0.03=3~5)
P0.04 Run command mode selection
Range: 0~5【0】
0: Keyboard control
1: Terminal control 1 (STOP invalid)
2: Terminal control 2 (STOP valid)
3: Serial communication 1 (STOP invalid)
4: Serial communication 2 (STOP valid)
5: Terminal control 3 (STOP and JOG invalid)
Note 1:
◆Keyboard control: Control the inverter Start and Stop by pressing the “RUN” key and
“STOP/RESET ” key on the keyboard.
◆Terminal control: The user should define X1~X8 terminal to achieve RUN, F/R, FWD,
REV, HLD and other running functions(see P3.01~P3.08) first, and then used the
terminals to control the inverter Start, Stop .etc.