Chapter 5 Parameter Introductions
Range: 0.5-10.0s This value depends on the
inverter model
P1.16 Trip-free time
Note:
If having the speed track optional parts, P1.15 could set to 1 or 2.
If under voltage occurred in trip-time, the inverter will display Uu alarm only, and the
motor cannot startup at this time. As shown in Fig. 5-1-7:
If under voltage occurred in running, the inverter will display “Uu” alarm and “Uu1”
fault, as shown in Fig.5-1-7. And PWM output inhibited, motor runs at zero-speed. If
the voltage recovered, “Uu” alarm will disappear,
If Uu1 fault occurred, the inverter will stop .If the voltage continues to drop to below
300V, a failure history record or a fault output will not happen. However, if the voltage
restored, the system will record the Uu1 fault.
Power 1 ON
OFF
ON
Trip-free
time
Treatment 0 RUN
Treatment 1 RUN
Treatment 2 RUN
Uu1 Uu1 Uu1 ... Recorded
Uu
Ze ro -s pe e d
Uu1 Uu1 ... Recorded
Uu Uu Not record
Ze ro -s pe e d
Zero-sp eed
Power 2 ON
OFF
Trip time
Treatment 0 RUN
Treatment 1 RUN
Treatment 2 RUN
Uu1 Uu1 Uu1 ... Not recorded
Uu
Zero-speed
Uu1 Uu1 ... Not recorded
Uu Uu Not recorded
Zero-speed
Zero-sp eed
Fig. 5-1-7 Trip-free diagram
119