◆The inverter can set three jump frequency points, and the jump frequency bandwidth
can overlap or nesting. If overlapped, the range broadens. When all three jump
frequency set to 0.00 Hz, the jump function will be disabled.
Range: 0.00~Max frequency
P2.11 Multi-step frequency 1
【5.00Hz】
Range: 0.00~Max frequency
P2.12 Multi-step frequency 2
【10.00Hz】
P2.13 Multi-step frequency 3
Range: 0.00~Max frequency
【15.00Hz】
P2.14 Multi-step frequency 4
Range: 0.00~Max frequency
【20.00Hz】
P2.15 Multi-step frequency 5
Range: 0.00~Max frequency
【30.00Hz】
P2.16 Multi-step frequency 6
Range: 0.00~Max frequency
【40.00Hz】
P2.17 Multi-step frequency 7
Range: 0.00~Max frequency
【50.00Hz】
Note:
◆Define Multi-step frequency respectively, which can be used in Multi-step speed
running and simple PLC running.
◆If P0.03 is set to 3 to 5 (P0.03=3~5), P0.01 is set to 9 (PID), P2.11 defined the
analog PID amplitude.
P2.18 Acc time 2
Range: 0.1~3600s【6.0/20.0s】
P2.19 Dec time 2
Range: 0.1~3600s【6.0/20.0s】
P2.20 Acc time 3
Range: 0.1~3600s【6.0/20.0s】
P2.21 Dec time 3
Range: 0.1~3600s【6.0/20.0s】
P2.22 Acc time 4
Range: 0.1~3600s【6.0/20.0s】
P2.23 Dec time 4
Range: 0.1~3600s【6.0/20.0s】
Note:
◆Define Acc/Dec time 2, 3 and 4 respectively (Acc/Dec time 1 is defined in P0.21 and
P0.22). Acc/Dec time 1, 2, 3 and 4 can be selected through external terminals, set by
P3.01~P3.08. If all terminals related with Acc/Dec time are invalid, the inverter will
take Acc/Dec time 1 as Acc/Dec time. However, when the inverter chooses PLC or
JOG operation, Acc/Dec time will not be controlled by external terminals, but be set
by parameter of PLC or JOG.