Chapter 5 Parameter Introductions
rising edge, so it must be operated as “disabled-enabled-disabled”, shown in Fig.
5-3-1.
Reset command
Keyboard display
w arning display
Normal display
Operation Freq.(Hz)
Run command
Time
Fig. 5-3-1 Terminal reset
7:FC: Setting frequency selection
◆If setting is 7: If P0.03 is set to 1, the operation frequency setting mode can be selected
by FC function terminal. If FC terminal is enabled, frequency setting set will be
determined by P0.02 (frequency setting 2); if FC terminal is disabled, frequency
setting set will determined by P0.01 (Frequency setting 1). With FC terminal, user can
switch the frequency set mode when the inverter is in running state. This function can
make the output frequency control more flexible.
8~9:Jog operation signal (FJOG/RJOG)
◆If setting is 8 or 9, this terminal can enable jog operation, when inverter didn’t start up
by other running command. FJOG is for jog forward command and RJOG is for jog
reverse command, as shown in Fig.5-3-2. The defined Jog function of terminal isn’t
limited by run command mode selection (P0.04).When Jog frequency, and jog
Acc/Dec time can be defined in P2.00~P2.02.
Operation Freq.(Hz)
P2.00
JOG
Time
Fig. 5-3-2 JOG operation
10~12: UP/DOWN
◆If P0.03 is set to 2, frequency setting will be the sum of frequency setting 1 and
frequency setting 2.