Chapter 5 Parameter Introductions
frequency reference of UP/DOWN will keep the initial value even if press
“STOP/RESET ” key. As shown in Fig.5-3-4.
13: FRE Coast-to-stop
If the setting value is 13 and the function terminal is effective, the inverter will stop
PWM output immediately, and exit from running state. Running command is only
active after release of terminal FRE. No matter what selection is set to P0.04 (Run
command mode selection) and what mode is set to P1.08 (stop mode), the FRE
Coast-to-stop function will take effect if the terminal function has been defined and
enabled.
14: Forced outage (Dec to stop within Dec time 4)
36: Forced outage normally close
The inverter stops according to Dec time 4, and decided by P1.08 (stop mode).
Operation Freq.(Hz)
UP/DOWN
reference Initial
Run Command
UP command
DOWN Command
Stop command
UP/DN reference amplitude
Fig. 5-3-4 UP/DOWN non-combination operation diagram
15: DC injection braking
If the function of terminal is defined as set DC injection braking, the terminal can be
used to perform DC injection braking. DC injection braking frequency at start, DC
injection braking time at start and DC injection braking current are defined by
P1.09~P1.11. Braking time is the max of P1.12 and the last time during which the DC
injection braking control terminal is active. As shown in Fig. 5-3-5.