Chapter 5 Parameter Introductions
Range: 0.01~99.99Hz/s【1.00Hz/s】
P3.10 Terminal UP/DN rate
Range:0.00~Frequency upper limit【10.00Hz】
P3.11 UP/DN reference amplitude
Note:
◆Terminal UP/DN rate is used to define the change rate of reference frequency that is
changed by terminal UP/DN. UP/DN reference amplitude used to define that the span
of reference frequency is changed by terminal UP/DN.
P3.12 Digital frequency UP/DOWN save
selection
Range: 0~2【2】
0: Receive STOP, UP/DN reference is reset to zero;
1: Receive STOP, UP/DN reference is not reset to zero, and not saved when power
loss;
2: Receive STOP, UP/DN reference is not reset to zero, and saved when power loss. If
P0.01is set to 1, P0.00 will be saved when power loss
Note:
◆UP/DOWN running is shown in Fig. 5-3-3 and Fig. 5-3-4.
◆When P0.01is set to 1: if P3.12 is set to 2 , the changed value of P0.00 by keyboard
digital encoder will be saved when power loss. Otherwise, the changed value won’t
be saved. For details, please refer to P0.00.
Range: 0~30【0】
P3.13 Define Functions of terminal DO
Range: 0~30【1】
P3.14 Terminal Y1 function definition
P3.15 Terminal Y2 function definition
Range: 0~30【2】
P3.16 Output function of Relay 1 (TA/TB/TC)
Range: 0~30【19】
P3.17 Output function of Relay 2
(BRA/BRB/BRC)
Range: 0~30【0】
Note:
For model 3004GB and the belows, function code P3.14, P3.15 are reserved and cannot
been modified. At the same time ,output function No. 26 and 27 are reserved , there is
no output; Function code P3.17 is used for “the terminal output hold time setting of
fixed-length arriving”. The details are below:
◆This series inverter has 5 digital outputs. The multi-function output terminals, D0, Y1,
Y2, Relay 1, and Relay 2 are programmable. They can be selected to output some
controlling and monitoring signal according to the application requirement. Refer to
Table 5-3-5.