User manual
Chapter 5 Parameter Introductions
139
Setting Function Description
22
Reserved Reserved
23
OLP2: Overload
signal
If the output current is higher than the value defined by
Pd.02 (Overload detection), the output of terminal is
valid.
24
Analog signals 1
abnormal
If analog signal 1 level is lower than the minimum
signal and lasts 500 ms, the output of terminal is valid.
25
Analog signals 2
abnormal
If analog signal 2 level is lower than the minimum
signal and lasts 500 ms, the output of terminal is valid.
26
STEP: Program
Running steps
Running steps of instruction program and the
corresponding procedure, and outputs, refer to Table
5-3-4. , the output of terminal is valid.
27
Fault type output
See Table 5-3-4 for faults that correspond to the output
signal.
28
Fixed-length
arriving
If the actual length defined by P8.01 is longer than the
length defined by P8.00, the output of terminal is valid.
29
Standby
If the inverter is in standby state, the output of terminal
is valid.
30 Zero-speed
If output frequency is zero, the output of terminal is
valid.
P3.17 Preset operating time(3004GB
and below models)
Range: 0.0~3.0s 【1s】
Note:
For model 3004GB and belows: function code P3.17 is valid for fixed-length
arriving hold time setting .For models above ,P3.17 is the Output function of
Relay 2.See description of P3.16 above;
When P3.13=28 or P3.16 =28, the DO or Relay1 output is selected as
"fixed-length arriving”, the setting of P3.17 will be effective.
When the P3.17 is set as 0: fixed-length arriving output terminal will hold the
output level until the length is reset.
When the P3.17 is set not as 0: the value of P3.17 will be the time during which the
fixed-length arriving output terminal will keep the output level .
P3.18 FAR detection width
Range: 0.00~10.00Hz【2.50Hz】
Note: