User manual
Chapter 5 Parameter Introductions
P3.23 Torque detection reference
Range: 0.0~200.0%【100.0%】
Note:
◆If motor torque is equal to or more than the range of torque detection reference, the
output of terminal is valid. If the motor torque is less than 80% of reference, the
output of terminal is invalid, as shown in Fig. 5-3-11.
Output torque
Torque detection
reference
Torque arriving
detection signal
Time
Torque detection
reference*80%
Torque arriving
detection
Fig. 5-3-11 Torque arriving detection threshold
P3.24 Preset Count value
Range: 0~9999【0】
Note:
◆If the counting value is bigger than the value defined by P3.24, the output of terminal
is valid, as shown in Fig. 5-3-12.
12345678
Xi Input
Counting value
arriving output
Preset Counting value
Fig. 5-3-12 Count value arriving
Range: 0.0~6553.5s 【0.0】
P3.25 Preset timing arriving
Note:
◆ When the timing time reaches the preset timing arriving (P3.25), the output of
terminal is valid, as shown in Fig. 5-3-7.
◆ The unit of timing time is up to function terminal. The total timing time will be
cleared to zero only when the terminal 49 is disabled, or continue accumulating.
P3.26 Preset operating time
Range: 0~65530h 【65530】
Note:
◆When the total operating time reaches the preset operating time (P3.26), the output of
terminal is valid.
142