Chapter 5 Parameter Introductions
5.5 Analog and Pulse Function (Group P4)
P4.00 Analog Nonlinear Selection
Range: 030
0:Null 1:AI1
2:AI2 3:Pulse
Note:
If the setting is 0, P4.01P4.05 are used to define AI1 inputs, P4.06P4.10 are used
to define AI2 inputs, and P4.11P4.15 are used to defined pulse inputs. They are
independent and have no interference with each other.
If the setting is not 0,it will be nonlinear selection, all the parameters from P4.01 to
P4.15 are setting points for the selected channel by P4.00. The filter time according to
the selected channel setting and the physical value of the others are 0.
If the setting of P4.00 is 1 or 2, the selection will be analog input and the default values
to each channel arranged from small to great are: 0.00V, 2.00V, 4.00V, 6.00V, 8.00V,
10.00V;
If the setting is 3, the selection will be pulse input. While the default input to the
channel are: 0.00 kHz, 10.00 kHz, 20.00 kHz, 30.00 kHz, 40.00 kHz, and 50.00 kHz.
The default physical values are linear relation.
Tips:
Only when the value of P4.00 is changed and saved by pressing the “ENTER” key, the
input channel value can be initialized to the default value.
P4.01 Min analog value Input 1 (AI1 Terminal)
Range: 0.0~P4.030.10V
P4.02 Physical value 1 corresponding to Min
analog value Input
Range: 0.0~100.0%0.0%
P4.03 Max analog value Input 1 (AI1 Terminal)
Range:P4.01~10.00V10.00V
P4.04 Physical value 1 corresponding to Max
analog value Input
Range: 0.0~100.0%100.0%
P4.05 Analog input filter time constant 1 (AI1
Terminal)
Range: 0.01~50.00s0.05s
P4.06 Min analog value Input 2 (AI2 Terminal)
Range: 0.00~P4.080.10V
P4.07 Physical value 2 corresponding to Min
analog value Input
Range: 0.0100.0%0.0%
P4.08 Max analog value Input 2 (AI2)
Range: P4.0610.00V10.00V
P4.09 Physical value 2 corresponding to Max
analog value Input
Range: 0.0100.0%100.0%
P4.10 Analog input filter time constant 2 (AI2
Terminal)
Range: 0.0150.00s0.05s
P4.11 Min pulse value Input 3 (pulse input
Terminal)
Range: 0.00P4.13 0.00K
P4.12 Physical value 3 corresponding to Min
pulse value Input
Range: 0.0100.0%0.0%