Chapter 5 Parameter Introductions
T1 T2 T3 T4 T5 T6 T7
Run Command
f1
f2
f3
f4
f5
f6
f7
Operation Freq.(Hz)
Time
Fig. 5-5-2
Holding the frequency after single cycle
◆Continuous operation
The inverter will start next cycle of operation automatically after completing one
cycle of PLC operation until receiving stop command. As shown in Fig. 5-5-3.
T1 T2 T3 T4 T5 T6 T7
Run command
f1
f2
f3
f4
f5
f6
f7
Operation Freq.(Hz)
Time
T1 T2 T3 T4 T5 T6 T7
f1
f2
f3
f4
f5
f6
f7
T1 T2
f1
f2
First cycle
Second cycle
Stop command
Fig. 5-5-3 Continuous operation of PLC
Range: 0~2【0】
P5.01 PLC restarting mode selection
0: Restart from first step
1: Continue from the step where the inverter stops
2: Continue to operate at the frequency when the inverter stops
Note:
◆Restart from first stage
If the inverter stops during PLC operation because of receiving stop command or fault,
or power loss, it will restart from the first step after restarting.
◆ Continue from the step where the inverter stops
When the inverter stops during PLC operation because of receiving stop command
148