User manual

Chapter 5 Parameter Introductions
mode 2.
P5.02 Saving PLC status when power off
Range: 010
0:Not save 1:Save
Note:
Not save
The inverter does not save the PLC operating state when the power is off and restart
from the first stage after the power is on.
Save
The inverter will save the PLC operating parameters such as the PLC operating stage,
PLC operating frequency, and PLC operating time when power is off. The inverter
will continue the PLC operation from the status of power off after the power is on.
P5.03 Unit of step time
Range: 010
0: Second 1: Minute
Note:
This unit is only valid for defining the PLC operating time. The unit of Acc/Dec time
in PLC operation is still second.
P5.04 Operating Timing T1
Range: 0.0360010.0
Range: 0.0360010.0
P5.05 Operating Timing T2
P5.06 Operating Timing T3
Range: 0.0360010.0
P5.07 Operating Timing T4
Range: 0.0360010.0
P5.08 Operating Timing T5
Range: 0.0360010.0
P5.09 Operating Timing T6
Range: 0.0360010.0
P5.10 Operating Timing T7
Range: 0.0360010.0
Note:
Configure the operating time of each PLC operating step. The range is 0.003600s
(The time unit can be select by P5.03. The default time unit is second). If the operating
time of the step is set to 0, the inverter will skip the step and run at the next step,
P5.11 Step T1 program operating setting
Range: 1 F4 r1F
Range: 1 F4 r1F
P5.12 Step T2 program operating setting
P5.13 Step T3 program operating setting
Range: 1 F4 r1F
P5.14 Step T4 program operating setting
Range: 1 F4 r1F
P5.15 Step T5 program operating setting
Range: 1 F4 r1F
P5.16 Step T6 program operating setting
Range: 1 F4 r1F
P5.17 Step T7 program operating setting
Range: 1 F4 r1F
Note:
P5.11~P5.17 are used to set the direction and Acc/Dec time of each PLC operating
step. Total 8 kinds of combinations, which is shown in Table 5-5-1, could be selected.
150