Chapter 5 Parameter Introductions
Range:
The inverter model of no more than 4kW:
0.00650.0Hz0.00Hz
P6.02 Preset of wobble frequency
The inverter model of no less than 5.5kW:
0.00400.0Hz0.00Hz
P6.03 Holding time before wobble
frequency operating
Range: 0.03600s0.0s
P6.04 Wobble frequency amplitude
Range: (0.050%) of P0.00 0.0%
P6.05 Skip frequency
Range: (0.050%) of P6.04 0.0%
P6.06 Skip Time
Range: 550ms5ms
P6.07 Wobble frequency operating
cycle
Range:0.1999.9s 10.0s
P6.08 Wobble ratio
Range: 0.110.01.0
Note:
P6.02 is used to define the operating frequency before entering wobble frequency
operation mode.
P6.03 is used to define the time when the inverter operates at wobble-preset
frequency.
P6.04 is used to define the range of wobble operating frequency. The actual value is
P0.00×P6.04.
P6.07 is used to define a cycle of wobble frequency operation including rising and
falling processes.
P6.08 is used to define wobble ratio, which is the ratio of UP time to DOWN time.
Range: 0,10
P6.09 Random wobble selection
Range: 0.11010
P6.10 MAX ratio of random wobble
P6.11 MIN ratio of random wobble
Range: 0.1100.1
Note:
P6.09 is used to select a fixed wobble ratio value defined by P6.08 or a random value
between P6.11~P6.10.
Wobble frequency operation has two starting modes:
Auto mode: If the setting of P0.01 is 10, the inverter will enter wobble frequency
operation mode automatically when power is on.
Manual mode: When the setting of P0.01 is not 10, the inverter first operates at other
defined mode. Then if the multi-function terminal (Xi is set to 45) is valid, the inverter
will enter wobble frequency operation mode.
Distinction: Compared with the auto mode, the manual mode omits the operating at
preset frequency.