Chapter 5 Parameter Introductions
deviations occur and the regulation time is longer. Only the right differential time can
reduce regulation time.
Range: 0.00~25.00s【0.00s】
P7.08 PID delay time constant
Note:
◆P7.08 set the output frequency delay time of PID.
P7.09 Residual margin
Range: 0.0~999.9【0.2】
Note:
◆If the residual between feed and feedback value is smaller than residual margin, PID
regulation will stop and the PID output maintain constant. As shown in Fig. 5-7-1.
◆Setting this parameter correctly is helpful to balance the system output accuracy and
stability. The residual margin reduces the regulation accuracy of the system, but
improves the system stability, to avoid unnecessary fluctuations of output.
◆If analog PID is selected, the setting of residual margin (P7.09) is the absolute value of
physical value, and it must match the measuring range. If speed PID is selected, the
setting of P7.09 is speed. As shown in Fig.5-7-1:
Time
Time
Reference
Feedback
Residual margin
Opereation Freq.
Fig. 5-7-1 Residual margin diagram
P7.10 PID adjust characteristics
Range: 0,1【0】
0: Positive 1: Negative
Note:
◆Positive: When the PID output increases, the output frequency will increase and the
controlled physical value will increase, such as waterworks.
◆Negative: When the PID output increases, the output frequency will increase, but the
controlled physical value will decrease, such as refrigeration system.
156