In order to reduce interference and attenuation of control signal, the length of control
cables should be limited in 50 m and away from power cables for more than 30 cm.
Avoid control wire and power wire being parallel. Try to use STP (Shielded Twisted Pair)
to connect analog input and output signal.
Function of Control Circuit Terminals
Table 2-8 Function of control circuit terminals
Category Terminal
Name Functions Specifications
Analog
input
AI1
Analog
input1
Be able to accept
voltage/current input.
Data-chosen-switch
SW1 can select
voltage or current
input mode. Voltage
input mode is the
default mode, refer to
P4.00P4.10 to set
the range.(The
reference ground is
GND)
Input voltage range:
010 V
(Input resistance:
100 k)
Input current range:
020 mA
(Input resistance:
500)