User manual
Chapter 5 Parameter Introductions
if it cannot reach the setting then set P8.06 positive. Now suppose that one motor is
overshoot, after doing the corresponding parameter settings ,the running process is as
shown in Fig.5-8-2.
P8.00+P8.06
t
L
P0.21
t
f
P0.00
P0.09
P0.21
actual frequency
Deceleration
point
sliding
stop
overshoot
P8.00
Actual Length
Fig. 5-8-2 Fixed length control diagram 2
Tips:
The actual length can be cleared by multi-function input terminal (Define terminal Xi
as No.52 function). The actual length will be calculated only after this terminal is
disconnected.
Actual length (setting of P8.01) will be saved automatically when the power is off. If
the operation frequency is greater than frequency upper limit and no pulse is input after
the running time is longer than 30 seconds, the inverter reports pulse coder fault (dE)
when actual length is 0.
If P8.00 is set to 0, function of stop at fixed length is disabled, but the calculated length
is still effective.
The setting value must increase 200.0mm when P8.06 is modified by MODBUS
communication. The corresponding relation between communication value and actual
used value (which can be displayed on the keyboard) is as follows:
Reality used value (displayed on the keyboard)) = Communication setting – 200.0mm
5.10 Advanced Control (Group P9)
P9.00 Gain of slip frequency compensation
Range: 0.0~200.0%【0.0%】
P9.01 Slip compensation time const
Range: 0.01~2.55S 【0.20S】