Chapter 5 Parameter Introductions
Linear speed = rotate speed × PC.22 (PG)
Reference linear speed= reference frequency* PC.22 (non PG)
Reference linear speed= reference speed × PC.22 (PG)
Tips:
The range of Display:
Linear speed and Reference: 0.00065.53m/s
Output power 0999.9 kW
Output torque 0300.0%
Output voltage 0999.9V
Bus voltage 01000V
AI1/AI2 0.0010.00V
External counting value 065530
Actual length/Preset length 0.00165.53m
5.14 Protection and Fault Parameters (Group Pd)
Pd.00 Motor overload protection mode
selection
Range: 021
0: Disabled
1: Common motor (with low speed compensation)
2: Variable frequency motor (without low speed compensation)
Note:
Disabled
The overload protection is disabled. Be careful to use this function because the
inverter will not protect the motor when overload occurs;
Common mode (with low speed compensation)
Since the cooling effects of common motor deteriorates at low speed (below 30 Hz),
the motor’s overheat protecting threshold should be lowered, which is called low
speed compensation.
Variable frequency motor (without low speed compensation)
The cooling effects of variable frequency motor are not affected by the motor’s speed,
so low speed compensation is not necessary.
Pd.01 Electro-thermal protective value
Range: 20110%100%
Note:
In order to apply effective overload protection to different kinds of motors, the Max
output current of the inverter should be adjusted as shown in Fig.5-13-1.