User manual

Chapter6 Troubleshooting
Fault
display
Name of
protection
Possible reasons of fault Actions
GF Ground Fault
Grounding current of
output side exceeds
specified value
Check whether the
insulation of the motor
become bad
Check whether the cable
connecting the inverter
and the motor is damaged
Heatsink
overheat
Ambient temperature is
too high
Obstruction of
ventilation channel
Cooling Fan does not
work
Lower the ambient
temperature
OH1 Clean the ventilation
channel
Replace the cooling fan
OL1
Motor
overload
Inverters output exceed
the over loading value
of the motor
Improper V/F curve
Low AC supply voltage
Common motor has
operated with heavy
load at low speed for a
long time
Load changes fast
Reduce the load
Adjust V/F curve and
torque boost
Check the AC supply
voltage
Use a special motor if the
motor is required to
operate for a long time
Check the load.
OL2
Inverter
overload
Inverters output exceed
its overloading value
DC injection braking
current is too big
Improper V/F curve
Low AC supply voltage
Too heavy load
Too short accelerating
time
Reduce the load, increase
accelerating time
Reduce the DC injection
braking current, increase
braking time
Adjust V/F curve and
torque boost
Check the AC supply
voltage
Select bigger capacity
inverter.
Increase accelerating time
SC
Load
short-circuit
Inverter’s output load is
short circuited
Check resistance of the
motor’s winding
Check the insulation of the
motor
186