Chapter6 Troubleshooting
Fault
display
Name of
protection
Possible reasons of fault Actions
External fault
comes from
RS485 serial
communicatio
n
MODBUS serial
transmission error
Faults comes from
external control circuit
Set correct overtime
detecting time or set
overtime detecting time of
Pb.03 to 0.0s
Check external control
circuit
EF0
Check input terminals, if
the fault appeared even
when the terminals aren’t
used, please, seek tech
support
EF1
External fault
on terminals
X1X8
SP1
Input phase
failure or
Unbalance
Input R,S,T have phase
loss or imbalance
Check input voltage
Check input cable
connection
Output phase
failure or
Unbalance
Output U,V,W have
phase loss or imbalance
Check output cable
connection
Check the insulation of the
motor and cables
SP0
Control circuit
fault0
The inverter connect
keyboard once after
electrifying, then
transmitting fault
continue for 2 seconds
or above(during
operating)
Reconnect the keyboard
Check connection cable of
keyboard
Replace the keyboard
CCF1
Replace the control board
CCF2
Control circuit
fault1
Transmission between
the inverter and
keyboard is established
once after supplying
power, but later
transmission fault
continues for more than
2 seconds.
CCF3
EEPROM
fault
EEPROM fault of the
control board
Replace the control board
AD
conversion
fault
CCF4
AD conversion fault of
the control board
Replace the control board