User manual
Appendix3 Main Circuit Output Cable Selection (Recommended)
Appendix 3 Main Circuit Output Cable Selection (Recommended)
Voltage
(V)
Power
grade
(kW)
The maximal length of output cable(m)
Wire
gauge
(mm2)
Without output reactor With output reactor
No
Shielded
Cable
( m)
Shielded
Cable
(m)
No
Shielded
Cable
(m)
Shielded
Cable
(m)
220
0.4 kW 2.5 110 80 150 105
0.75kW 2.5 110 80 150 105
1.5kW 4 180 150 230 175
2.2kW 4 180 150 230 175
380
0.75kW 2.5 110 80 150 105
1.5kW 2.5 110 80 150 105
2.2kW 4 180 150 230 175
4kW 4 180 150 230 175
5.5kW 4 200 160 250 185
7.5kW 6 200 160 250 185
11kW 6 200 160 250 185
15kW 6 200 160 250 185
18.5kW 10 200 160 250 185
22kW 16 200 160 250 185
30kW 25 220 180 280 210
37kW 25 220 180 280 210
45kW 35 240 200 320 250
55kW 35 240 200 320 250
75kW 70 260 220 380 260
93kW 70 260 220 380 260
110kW 95 260 220 380 260
132kW 150 260 220 380 260
160kW 185 280 240 440 340
185kW 185 280 240 440 340
200kW 240 280 240 440 340
220kW 150*2 300 260 500 400
250kW 185*2 320 280 550 430
213