Chapter 2 Installation and Wiring
22
Category Terminal
Name Functions Specifications
Power
supply
PE
Shielding
ground
It is used for
grounding of
shielding layer. The
shielding layer of
analog signal
lines,communication
line 485 and motor
cable can be
connected to this port.
It is connected to the
terminal PE in main
circuit.
2.5.2 Control Circuit Wiring
Wiring analog input terminal
AI1/AI2 can accept analog signal input, operate Data-chosen-switch SW1 to select input
voltage (010V) or input current (020mA).The wiring is shown as Figure 2-13:
0~+10V
Or 0~20mA
GND
AI1/AI2
PE
1 2
ON
AI1 AI2
I
V
Shielded wire near
Grounding
SW1
Inverter
Fig 2-13 Analogy input terminal wiring diagram
Wiring analog output terminal
In S2R4GB3004GB, if the analog output terminal AO1 is connected to analog meters,
the various kinds of physical values can be indicated. Operate wiper switch SW2 to
select output voltage (0/210 V) or output current (0/420 mA).The wiring is shown
as Figure 2-14: