Chapter 4 Parameter Index
88
Function
code
Function
Name
LCD
Display
Range of settings
Default
Change
MODBUS
Address
P7.01
PID
feedback
selection
PID
feedback
selection
0: AI1 terminal
1: AI2 terminal
2: Serial
communication
3: Pulse feedback
4: |AI1-AI2|
5: Reserved
7: MIN (AI1,
AI2)
8: MAX (AI1,
AI2)
9: PG or
single-phase
speed
measuring
input
1
× 0801
P7.02
Analog
PID digital
feed
Analog
PID digital
feed
0.0999.9
0.0
0802
P7.03
Speed PID
feed
Speed PID
feed
024000rpm
0rpm
0803
P7.04
Reserved Reserved Reserved 1
- 0804
P7.05
PID
proportion
al gain
(KP)
PID
Proportiona
lity
Coefficient
0.19.9
1.0
0805
P7.06
PID
integration
time
PID
integration
time
0.00100.0s
10.00s
0806
P7.07
PID
differential
time
PID
differential
time
0.001.00s
0.00s
0807
P7.08
PID delay
time
constant
PID delay
time
0.0025.00s
0.00s
0808
P7.09
Residual
margin
Residual
margin
0.0999.9
0.2
0809
P7.10
PID adjust
characterist
ics
PID adjust
characterist
ics
0: Positive
1: Negative
0
× 080A