User manual
Chapter 4 Parameter Index
93
Function
code
Function
Name
LCD
Display
Range of
settings
Default
Change
MODBUS
Address
PA.05
Leakage
inductance
%X
Leakage
inductance
%X
0.00%~50.00%
This
value
depends
on the
inverter
model.
○ 0B05
PA.06
Resistance
of
rotor %R
2
Resistance
of
rotor %R2
0.00%~50.00%
This
value
depends
on the
inverter
model.
○ 0B06
PA.07
Mutual
inductance
Xm
Mutual
inductance
Xm
0.0%~200.0%
This
value
depends
on the
inverter
model.
○ 0B07
PA.08
Rated
Speed
Rated
Speed
0~24000 rpm
This
value
depends
on the
inverter
model.
○ 0B08
PA.09
Reserved Reserved Reserved 0
- 0B09
Pb
: MODBUS Communication
Function
code
Function
Name
LCD Display
Range of
settings
Default
Change
MODBUS
Address
Pb.00
MODBUS
Baud rate
selection
Baud rate
selection
0: 1200 1:
2400
2: 4800 3:
9600
4: 19200
5: 38400
3
× 0C00
Pb.01
MODBUS
slave
address
MODBUS
slave address
1~31
1
× 0C01
Pb.02
MODBUS
parity
selection
Parity bit
selection
0: Even parity
1: Odd parity
2: No parity
0
× 0C02