Operating instructions

6. INSTALLATION
31
6.10 APM (Automatic Performance Monitor)
The APM is a field-replaceable logic upgrade that allows the XM Series power module
to self-test the inverter and batteries at pre-determined intervals and durations. It also
allows the battery charger's equalize voltage (interval and duration) to be pre-selected to
further optimize battery performance. The APM logic card plugs directly onto the main
control board at connector J2 (see illustration on previous page). Note: The Main Circuit
Module assembly must be completely removed from the power module when installing the
APM.
6.10.1 APM "Auto-Test" Interval and Duration Selection
Select self-test interval and duration settings at switch (S402) located on the APM
logic card (see previous page). Positions 1, 2, 3 or 4 determine the test intervals; posi-
tions 5, 6 or 7 determine the test duration. When a DIP switch is in the ON position, the
mode is activated. If none of the switch positions are selected, the mode reverts to its
default setting (manual test only: 34 minute test duration on 60 Hz models; 40.8 minutes
on 50 Hz models). If two switch positions are accidently selected for either interval or
duration (i.e., 6 and 7), the mode reverts to the lower of the two settings. Note: DIP switch
#8 is used only to activate the "After Outage Equalize" (AOEQ) feature.
6.10.2 APM "Auto-Equalize" Interval and Duration Selection
Equalize increases the normal battery recharge voltage by the amount selected at the
main board jumpers (Section 6.9.2). This feature is used to automatically send an equalize
voltage to the batteries at predetermined intervals and durations. It is extremely useful in
maintaining equal charges among individual battery cells.
Select Auto-Equalize interval and duration settings at switch (S401) located on the
APM logic card (see previous page). Positions 1, 2, 3 or 4 determine the equalize inter-
vals; positions 5, 6, 7 and 8 determine the equalize duration. When a DIP switch is in the
ON position, the mode is activated. If none of the switch positions are selected, the mode
reverts to its default setting (manual equalize only: 2.3 hour equalize duration on 60 Hz
models; 2.8 hour equalize duration on 50 Hz models). If two switch positions are accidently
selected for either interval or duration (i.e., 3 and 4), the mode reverts to the lower of the
two settings.
The APM logic upgrade is also equipped with an "After Outage Equalize" (AOEQ)
feature that automatically activates equalize mode after
every outage. This allows se-
verely discharged batteries to be aggressively recharged after inverter operation to prepare
for the next utility power outage. This feature is extremely useful in areas where long
outages occur on a regular basis. AOEQ is activated by placing DIP switch #8 (S402) in
the ON position. The AOEQ duration is determined by the duration setting on the equalize
switch (S401). CAUTION: Possible battery damage can occur if used incorrectly. Always
refer to the battery manufacturer's recommendations for equalize charging before selecting
AOEQ.
Note: Interval and Duration settings must be selected. DIP switches must be in the ON
position to activate the mode.