7.3 Power Module Shutdown
When a power module needs to be removed from service, an Alpha APP60-S Service
Power Supply is recommended as an alternate non-standby power source to prevent
interruption to the cable plant. Note: When powering down a module, always switch the
battery breaker OFF before removing AC, otherwise the module will transfer into inverter
operation.
Procedure
1. Plug the APP60-S "Jones" connector into the SPI (Service Power Inserter).
2. Plug the APP60-S power cord into the enclosure's convenience outlet. Switch the
APP60-S ON. Note: Verify that the 30 / 60 VAC selector is in the desired position.
3. Toggle the switch on the SPI from "ON" to "ALT".
4. Switch the battery breaker on the side panel of the XM Series module OFF.
5. Unplug the XM Series module's power cord from the enclosure's convenience outlet.
6. Wait approximately 1 minute for the module's capacitors to fully discharge.
7. Remove the cables from the module's side panel connectors.
8. Carefully slide the power module out of the enclosure. CAUTION: The ferroresonant
transformer generates heat and may cause burns if handled with bare hands.
9. Reverse this procedure, when re-installing a module. Always test the power module
before toggling the SPI's switch from "ALT" to "ON".
7. OPERATION
APP60-S Service Power Supply
AC Input Fuse
41