Operating instructions

MAINTENANCE
Maintenance should be performed every three to six months. If the power module fails to
perform a specific function, refer to the troubleshooting chart. By establishing a routine
maintenance program and following the guidelines contained in this manual, the XP Series
power supply will continue to provide years of trouble-free operation.
Care of the batteries should be the first step in any power supply maintenance program.
In addition to voltage checks, visually inspect the batteries for signs of cracks, leaks or
swelling. To aid in quick identification and tracing of voltages in the maintenance log, number
the batteries inside the enclosure using labels or masking tape, etc. Because of a batterys
chemical composition, it is temperature sensitive and susceptible to over and under-charging.
Since batteries behave differently in the winter than they do in the summer, Alpha logic cards
automatically compensate for changes in temperature by adjusting float and equalize charge
voltages.
SAFETY PRECAUTIONS
THE POWER SUPPLY SHOULD BE SERVICED ONLY BY QUALIFIED PERSONNEL.
USE A BUCKET TRUCK, OR SUITABLE SAFETY EQUIPMENT (SAFETY HARNESS AND
CLIMBING SPIKES), WHEN SERVICING POLE-MOUNT INSTALLATIONS.
USE HEAVY GLOVES WHEN HANDLING A POWER MODULE THAT HAS JUST BEEN
TAKEN OUT OF SERVICE. THE FERRORESONANT TRANSFORMER GENERATES HEAT
AND MAY CAUSE BURNS IF HANDLED WITH BARE HANDS.
NEVER ATTEMPT TO RECALIBRATE A LOGIC CARD IN THE FIELD, OTHER THAN
SETTING BATTERY CHARGER VOLTAGE JUMPERS (SECTION 6.9) OR APM AUTO-
MATIC PROGRAM JUMPERS (SECTION 6.10).
ALPHA TECHNOLOGIES IS NOT RESPONSIBLE FOR BATTERY DAMAGE DUE TO
IMPROPER CHARGER VOLTAGE SETTINGS. REFER TO THE CHARGE VOLTAGE
CHART (SECTION 6.9) AND CONSULT THE BATTERY MANUFACTURER FOR CORRECT
CHARGE VOLTAGE REQUIREMENTS.
WHEN REMOVING BATTERIES, ALWAYS SWITCH THE MODULE'S BATTERY BREAKER
OFF BEFORE UNPLUGGING THE BATTERY CONNECTOR.
WEAR SAFETY GLASSES WHENEVER WORKING WITH BATTERIES.
Procedure:
8.1 Check Battery Terminals and Connecting Wires
Check each battery terminal and connection. Make sure the posts are clean and the
crimped connectors are tight. One major battery manufacturer suggests that terminal
connectors be torqued to 75 inch/pounds at installation and then re-torqued to 60 inch/pounds
during routine maintenance. If there is an "in-line" fuse in the battery cable, check the fuse
holder and fuse. Make sure the terminals are properly greased with an approved battery
terminal corrosion inhibitor such as NCP-2.
8.2 Check Battery Open Circuit Voltage
Switch the battery breaker on the side panel of the power module to OFF. Disconnect the
battery connector from the module and measure the individual voltage across each battery.
The difference between any battery in the string should not be greater than 0.3 VDC. Defective
or marginal batteries should be replaced with an identical type of battery.
43
8. MAINTENANCE