0 Owner manual

Q U I C K C H I LL E R I N S TA L L AT I O N / O P E R AT I O N /S E R VI C E M A N U A L 1 2 .
E L E C T R I C A L
I N S T A L L A T I O N
This appliance must be branch circuit protected with
proper ampacities, in accordance with the wiring
d
iagram. The Quickchiller must be properly
grounded in accordance with the National Electrical
Code and applicable local codes. Wire size for the
main incoming power to the unit must match the
minimum size listed in the specifications applicable
to the specific Quickchiller model. For supply
connections, locate the wire size listed in this manual.
Before operating the chiller, check all cable connections
in the electrical connection area for tightness since
connections can loosen during transport.
N O T E: After electrical connections have been
completed, operate the appliance in any
chilling mode for a period of 15 minutes
and recheck the main power connections at
the terminal block to make certain they
remain tight.
D A N G E R
To avoid electrical shock, this
a
ppliance MUST be adequately
grounded in accordance with local
electrical codes or, in the absence of
local codes, with the current edition
of the National Electrical Code
ANSI/NFPA No. 70. In Canada, all
electrical connections are to be
made in accordance with CSA C22.1,
Canadian Electrical Code Part 1 or
local codes.
D A N G E R
ELECTRICAL CONNECTIONS MUST
BE MADE BY A QUALIFIED SERVICE
TECHNICIAN IN ACCORDANCE WITH
APPLICABLE ELECTRICAL CODES.
VOLTAGE PHASE CYCLE/HZ
Q C - 3 Q C - 2 0 Q C - 4 0 QC - 5 0 Q C - 1 0 0
S E L F - C O N TA I N E D
208-240VAC 1 ph 50/60 Hz
R
ECOMMENDED CIRCUIT AMPERAGE:
R
ECOMMENDED WIRE SIZE:
20 amps
12/2 w.g.
20 amps
12/2 w.g.
30 amps
10/2 w.g.
40 amps
8/2 w.g.
60 amps
6/2 w.g.
N O C O R D A N D P L U G
VOLTAGE PHASE CYCLE/HZ
Q C - 3 Q C - 2 0 Q C - 4 0 QC - 5 0 Q C - 1 0 0
S E L F - C O N TA I N E D
208-240VAC 3 ph 50/60 Hz
R
ECOMMENDED CIRCUIT AMPERAGE:
R
ECOMMENDED WIRE SIZE:
NOT AVAILABLE NOT AVAILABLE NOT AVAILABLE
20 amps
12/3 w.g.
40 amps
8/3 w.g.
380-415VAC 3 ph 50/60 Hz
R
ECOMMENDED CIRCUIT AMPERAGE:
R
ECOMMENDED WIRE SIZE:
NOT AVAILABLE NOT AVAILABLE
30 amps
10/2 w.g.
NOT AVAILABLE
30 amps
10/2 w.g.
N O C O R D A N D P L U G
VOLTAGE PHASE CYCLE/HZ
Q C - 3 Q C - 2 0 Q C - 4 0 QC - 5 0 Q C - 1 0 0
R E M O T E C O M P R E S S O R
( C a b i n e t O n l y )
208-240VAC 1 ph 50/60 Hz
R
ECOMMENDED CIRCUIT AMPERAGE:
R
ECOMMENDED WIRE SIZE:
NOT AVAILABLE NOT AVAILABLE NOT AVAILABLE
20 amps
12/2 w.g.
30 amps
10/2 w.g.
N O C O R D A N D P L U G
E L E C T R I C A L S P E C I F I C AT I O N S
Wire diagrams are located near the top of the unit, close to the compressor or control panel.