AS-H40Y - 12KW AS-H50Y - 15KW AS-H60Y - 18KW ALTOHeat Pump installation manual
CUSTOMER NAME........................................................................ POOL DEALER.............................................................................. DATE INSTALLED.......................................................................... SERIAL NO..................................................................................... MODEL...........................................................................................
HEAT PUMP- AS-H40Y 12kW 2
HEAT PUMP- AS-H50Y (15kW) & AS-H60 (18kW) 3
INSTALLATION AND SITING Prior to installing your heat pump:All heat pumps are factory assembled and tested prior to delivery. Please check for any external damage especially to the evaporator fins, please diagram below. Minor damage or indentations to the fins do not affect performance and can be remedied by your service contractor. If severe damage has occurred please contact your supplier immediately. Do not attempt to install heater unit.
PLUMBING Alto heat pumps are supplied with 1.5" BSP parallel threads, male. We strongly recommend a 1.5" female socket union is applied to inlet/outlets for future draining and servicing of the appliance. 2 x1.5” Female/Threaded Socket Unions Required Alto heat pumps must be installed in the return line after the filter. If an existing heater or back-up heater has been installed then the heat pump should be installed between the filter and the other heater.
Drw.2 Recommended plumbing layout when incorporating Solar Heating. If an increased flow rate is required instal a booster pump as per drw.4 below. Position for optional Erosion Feeder Back-Up Heater if required Non-Return Valve Pool Female/ Threaded Socket Union FILTER BACKWASH Non-Return Valve 3-Way Valve FILTER Ball Valve Condensate Water to waste PUMP Solar Heating Install a plumbing bypass for running filtration & heat pump at night. Drw.
Drw.4 Recommended plumbing layout when incorporating two heat pump units. IMPORTANT Minimum flow rate required to use this system is 3000 Litres / 660 Gallons (imperial) per hour.
ELECTRICAL CONNECTION & CIRCUIT DIAGRAM IMPORTANT. It is recommended that all electrical supplies and connections are carried out by a qualified electrician, in accordance with I.E.E. standards, latest issue, or local codes of practice as applicable. Also recommended is a protected supply to incorporate fuses or motor type circuit breakers (Type C) to specified rating (see Data Sheet page 18). An earth leakage trip (R.C.
CONTROL PANEL FUNCTIONS 1 0 4H0 1 2 3 1. When electric supply is connected the ‘Run’ power light will be on and the display panel will display the current water temperature. ie.10 H = 10°C. 2. On/OFF button to turn heater on and off - see page 10. 3. The ‘set’ button is used to set the F1-5 functions ie.water temperature, defrosting cycle and defrosting time etc.
CONTROL PANEL FUNCTIONS 1-3 When the ON/OFF buttons is pressed for the first time, the display panel will display the current water temperature and the desired pool temperature. eg. the display may read 10 40 ----- 10 is the current water temperature 10°C and 40 is the desired water temperature 40°C. Using the up and down buttons, you can set the swimming pool water to the desired temperature between +15°C up to + 65°C. NOTE.
CONTROL PANEL FUNCTIONS 4-5 When the SET button is pressed for the fourth time, the display panel will display:- F4 : Operation Mode. F4 C : Cooling Mode. F4 H : Heating Mode When the SET button is pressed for the fifth time, the display panel will display:- F5 : The defrosting temperature of the evaporator pipe. The recommended temperature should be set to -5°C. To adjust setting YOU MUST PRESS THE ON/OFF BUTTON FIRST.
FLOW METER area RED area RED area After the water heater has been running for more than 15 minutes, it will be running at full capacity. If you want to make the heat pump run more efficiently the water flow should be adjusted by checking the pressure meter display. If the meter index is in the green area, the water heater is running in the most efficient way and you do not need to adjust anything.
CONTROL PANEL FUNCTION - ERROR DISPLAY 1-4 IF THE HEATER STOPS WORKING ONE OF THE FOUR ERRORS WILL BE DISPLAYED THE FAILURE LIGHT WILL BE ON AND THE RELEVANT CODE WILL START TO FLASH E1: the water temperature sensor is not working correctly. E2 : the tube sensor is not working correctly. E3 : Pool filtration is running but water flow is not sensed. Water flow sensor is not working correctly or there is a lack of water flow.
AUTO RESTART AND DEFROSTING FUNCTION AUTO RESTART FUNCTION The Alto water heat pump has an auto restart function. When the power supply is switched off accidentally, it will automatically save the operation mode. When the power supply is restored, the unit will automatically restart after five minutes and operate in the same working mode. REVERSE CYCLE DEFROST FUNCTION When the ambient air temperature is too cold, the evaporator will start to freeze and frost will appear on the evaporator fins.
WATER CHEMISTRY The following water quality must be maintained at all times to prevent premature corrosion. It is recommended that your water balance is checked and balanced by a pool professional. Your warranty does not cover for damaged caused by poor water chemistry and neglect. pH: Total Alkalinity: Total hardness: Total Dissolved solids: Saline Water max: Chlorine Free Cl: Cyanuric level Super chlorination Max: Bromine: Baquacil: 7.2 -7.
ALTO WARRANTY POLICY This voluntary policy is supplemental to and in no way affects any statutory rights which the customer may have. 1 Warranties 1.1 Paramount Pools warrants the Alto Heat Pump for a period of one (1) year from the date installed for both parts and labour. 1.2 At the end of the first year the following warranties apply as to parts only; labour is excluded from these warranties:- 1.2.1 The condenser and compressor are warranted for three (3) years; 1.2.
HEAT PUMP SERVICE An Alto heat pump should give you many years trouble free service. However, to obtain the maximum efficiency from your heater Alto recommend that your heater is checked and serviced every 12 months. Service & extended warranty packages are available from a UK Service Agent (see contact detail below). HEAT PUMP BREAKDOWN If you think there is a problem with your heater and are not able to diagnose the fault please contact your POOL DEALER initially to discuss the symptoms.
ALTOHeat Pumps - SPECIFICATION Model No. AS-H40Y 12kW AS-H50Y 15kW AS-H60Y 18kW Heating Capacity (Btu/h) Cooling Capacity (Btu/h) Rated Input (w) Heating Cooling PTC Power (w) COP for Heating (w/w) (at 20 °C ambient air temperature) 40000 35000 50000 42000 60000 55000 2540 2465 -------4.42 3185 3020 -------4.40 3790 3900 -------4.44 Refrigerant R407C R407C R407C 230/1/50 11.3 10.9 -------32 230/1/50 14.1 13.4 -------36 230/1/50 16.8 17.