Installation manual
ELECTRICAL CONNECTION & CIRCUIT DIAGRAM
IMPORTANT. It is recommended that all electrical supplies and connections are carried out by a qualified
electrician, in accordance with I.E.E. standards, latest issue, or local codes of practice as applicable.
Also recommended is a protected supply to incorporate fuses or motor type circuit breakers (Type C) to specified
rating (see Data Sheet page 18).
An earth leakage trip (R.C.D) of the current operating type (30mA) is recommended to be fitted to all pool electric's.
Minimum/Maximum Voltage requirements.:
Single phase machines 50Hz 207v 253v
Three phase machines 50Hz 360v 440v
Cycle Frequency 50Hz 47.5Hz 52.5Hz
N.B. This voltage must be available at the heat pump whilst running.
AS-H40Y (12KW) AS-H50Y (15KW) AS-H60Y (18KW)
SINGLE PHASE (1-N 50HZ)
AS-H40Y (12KW) AS-H50Y (15KW) AS-H60Y (18KW)
SINGLE PHASE WITH SOFT START SYSTEM (1-N 50HZ)
8