Installation Manual
- 2 - AL1012ULXseries
Overview:
The AL1012ULX is a power supply that converts a 115VAC / 60Hz input to a 12VDC output (see specifications).
The AL1012ULX is a base unit for a series of UL Listed multi-output power supply/chargers including: AL1012ULXPD4,
AL1012ULXPD4CB, AL1012ULXPD8, AL1012ULXPD8CB, AL1012ULXPD16, AL1012ULXPD16CB (Refer to
AL1012ULX Series Power Supply Configuration Reference Chart below).
AL1012ULX Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory
Power
Distribution
Module(s)
Number of
Output(s)
Class 2 Rated
Power-
Limited
Output(s)
Fused Outputs
PTC Outputs
Output Rating
(amp) per
Output
Power Supply
Ouitput Fuse
Rating
Agency
Listings
UL Listings
and File
Numbers
AL1012ULX
----- 1 ----- ----- ----- 10 15A/32V
UL 294
(File # BP6714)
UL Listed for
Access Control
Systems.
“Signal Equipment”
Evaluated to
CSA Standard C22.2
No.205-M1983
AL1012ULXPD4
PD4UL 4 -----
3
----- 3.5 15A/32V
AL1012ULXPD4CB
PD4ULCB 4
3
-----
3
2.5 15A/32V
AL1012ULXPD8
PD8UL 8 -----
3
----- 3.5 15A/32V
AL1012ULXPD8CB
PD8ULCB 8
3
-----
3
2.5 15A/32V
AL1012ULXPD16
Two (2) PD8UL 16 -----
3
----- 3.5 15A/32V
AL1012ULXPD16CB
Two (2) PD8ULCB 16
3
-----
3
2.5 15A/32V
Stand-by: 15 minutes of Stand-by at 10 amps.
Specifications:
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8).
Secure enclosure to earth ground.
2. Connect AC power (115VAC / 60 Hz) to the terminals marked [L, N] (Fig. 1, pg. 5). Use 14 AWG or larger for all
power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/
Low Battery reporting).
Note: Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Mea sure output voltage before connecting device. This helps avoiding potential damage.
4. Connect devices to be powered:
a. For Power Supply Board: connect to the terminals marked [+ DC -] (Fig. 1, pg. 5).
Input:
• Input115VAC/60Hz,2.6amp.
• Inputfuserated@5A/250V.
Output:
• 12VDCoutput.
• 10amptotalsupplycurrentat12VDC.
• Filteredandelectronicallyregulatedoutputs.
• Shortcircuitandthermaloverloadprotection.
Battery Backup:
• Maximumchargecurrent0.7amp.
• Built-inchargerforsealedleadacidorgeltypebatteries.
Battery Backup (cont’d):
• Automaticswitchovertostand-bybatterywhen
AC fails.
• Zerovoltagedropwhenswitchedoverto
battery backup.
Supervision:
• ACfailsupervision(form“C”contacts).
• Batterypresenceandlowbatterysupervision
(form “C” contacts).
LED Indicators:
• ACinput,DCoutputandBATtroubleLEDindicators.
LISTED