Installation Instructions

AL1024NK8(D) Installation Guide - 3 -
Specifications:
Inputs:
AL1024ULXB2:
115VAC, 60Hz, 4.2A.
PDS8/PDS8CB:
24VDC from AL1024ULXB2.
12VDC from VR6 voltage regulator.
Outputs:
Power:
12VDC up to 6A, 24VDC up to 10A
(240W total power).
Overvoltage protection.
PDS8:
- Fuse protected outputs rated @ 2.5A per output,
non power-limited. Total output 10A max.
Do not exceed the individual power supply ratings.
PDS8CB:
- PTC protected outputs rated @ 2A per output,
Class 2 power-limited. Total output 10A max.
Do not exceed the individual power supply ratings.
Eight (8) selectable independently controlled outputs.
Individual outputs may be set to OFF position for
servicing (output switch set to middle position).
Any of the eight (8) fuse/PTC protected power
outputs are selectable to follow power Input 1 or
Input 2. Output voltage of each output is the same
as the input voltage of the input selected.
Surge suppression.
Fuse/PTC Ratings:
AL1024ULXB2:
- Input fuse is rated 5A/250V.
- Battery fuse rated 15A/32V.
PDS8:
- Input fuse is rated 10A/32V.
- Output fuses are rated 3A/32V.
PDS8CB:
- Input PTC is rated 9A.
- Output PTCs are rated 2A.
Supervision:
AC fail supervision (form “C” contacts).
Low battery supervision (form “C” contacts).
Battery presence supervision (form “C” contacts).
Battery Backup:
Built-in charger for sealed lead acid or
gel type batteries.
Automatic switch over to stand-by battery
when AC fails.
Maximum charge current 3.6A.
Zero voltage drop when switched over to
battery backup.
Visual Indicators:
AL1024ULXB2:
Green AC LED: Indicates 115VAC present.
Red DC LED: Indicates DC output.
PDS8(CB):
Individual voltage LEDs indicate 12VDC (Green)
or 24VDC (Green and Red).
Environmental:
Operating temperature: 0ºC to 49ºC ambient.
Humidity: 20 to 85%, non-condensing.
Enclosure Dimensions (approximate H x W x D):
15.5” x 12” x 4.5”
(393.7mm x 304.8mm x 114.3mm).