Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for
proper voltage level.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified
voltage both at the battery terminal and at the board terminals marked [– BAT +] to ensure
that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 3.6A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––