Spec Sheet
AL1024NKA8
Lifetime Warranty
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com
Rev. 12072021
AL1024NKA8D
Dual Voltage Access Power Controller with Power Supply/Charger
Altronix AL1024NKA8D converts a 115VAC 60Hz input into eight (8) PTC protected outputs.
Outputs are individually selectable, providing 12VDC or 5VDC up to 6A and/or 24VDC up to
10A (240W total power) for access control panels, door locks, and ancillary devices. Power
outputs can be converted to dry form āCā contacts. Outputs are activated by an open col-
lector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output from
an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. AL1024NKA8D will
route power to a variety of access control hardware devices including Mag Locks, Electric
Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-
Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may
be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually
selectable for any or all of the eight (8) outputs. The spade connectors allow you to daisy
chain power to multiple ACMS8 modules. This feature allows you to distribute the power
over more outputs for larger systems.
- Unit provides 12VDC or 5VDC up to 6A and/or
24VDC up to 10A (240W total power)
- Short circuit and overvoltage protection
- Supervision
- AC Fail
- Battery Fail and Battery Presence
- Bi-colored LEDs provide visual verification of
voltage on each output
- Stackable sub-assemblies save valuable space
- Built-in charger for sealed lead acid or gel type batteries
- Instantaneous transfer to stand-by batteries
- Eight (8) independently controlled outputs
- Eight (8) auxiliary power outputs (unswitched).
- Filtered and electronically regulated outputs
- Fire Alarm disconnect (latching or non-latching) is individually
selectable for any or all of the eight (8) outputs
- CE European Conformity
Key Features