Spec Sheet
- Unit provides 12VDC or 5VDC up to 6A and/or
24VDC up to 10A (240W total power)
- Short circuit and overvoltage protection
- Supervision
- AC Fail
- Battery Fail and Battery Presence
- Fire alarm disconnect
- Bi-colored LEDs provide visual verification of
voltage on each output
- Stackable sub-assemblies save valuable space
- Built-in charger for sealed lead acid or gel type batteries
- Instantaneous transfer to stand-by batteries
- Eight (8) independently controlled outputs
- Eight (8) auxiliary power outputs (unswitched)
- Filtered and electronically regulated outputs
- Fire Alarm disconnect (latching or non-latching) is individually
selectable for any or all of the eight (8) outputs
- Built-in LINQ technology facilitates monitoring, reporting, and
control of power supply/charger over the network
- Reports diagnostics via Email and Windows Dashboard
Alert notifications, greatly reducing system downtime
and eliminating unnecessary service calls
- CE European Conformity
Key Features
Rev. 02232022
AL1024NKA8DQM
Lifetime Warranty
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com
AL1024NKA8DQM
Networked Dual Voltage Access Power Controller with Power Supply/Charger
Altronix AL1024NKA8DQM converts a 115VAC 60Hz input into eight (8) PTC protected power-
limited outputs. Outputs are individually selectable, providing 12VDC or 5VDC up to 6A and/or
24VDC up to 10A (240W total power) for access control panels, door locks, and ancillary devic-
es. Power outputs can be converted to dry form āCā contacts. Outputs are activated by an open
collector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output from
an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. AL1024NKA8DQM
will route power to a variety of access control hardware devices including Mag Locks, Electric
Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure
modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to
trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any
or all of the eight (8) outputs. The spade connectors allow you to daisy chain power to multiple
LINQ8ACM(CB) modules. This feature allows you to distribute the power over more outputs for
larger systems. Built-in LINQ
TM
Network Power Management facilitates monitoring, reporting
and control of power/diagnostics.