Datasheet

Agency Approvals
Specifications
UL 294 UL Listed for Access Control
System Units.
UL 1481 UL Listed Standard for Safety for
Fire Protective Signaling Systems.
Input:
• Input115VAC/60Hz,4.4amp.
• Inputfuserated@3.5amp/250V.
Output:
• 24VDCoutput.
•10ampofcontinuoussupplycurrentfor
AccessControlapplications.
• 8ampofcontinuoussupplycurrentfor
FireAlarmapplications.
• Sixteen(16)Class2RatedPTCprotectedpower
limitedoutputs.
• Outputsarerated@2.5amp.
• Filteredandelectronicallyregulatedoutput.
• Shortcircuitandthermaloverloadprotection.
Battery Backup:
• Built-inchargerforsealedleadacidor
geltypebatteries.
• Automaticswitchovertostand-bybattery
whenACfails.
Battery Backup (cont’d):
• Maximumchargecurrent3.6amp.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
• Batterypresencesupervision(form“C”contacts).
Visual Indicators:
• ACinputandDCoutputLEDindicators.
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• 45-91BTU/Hr.:
• SystemACinputVArequirement:506VA.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
15.5”(393.7mm)x12”(304.8mm)x4.5”(114.3mm)
- Accommodatesuptotwo(2)12VDC/12AHbatteries.
• Productweight(approx.):10.1lbs.(4.58kg.).
• Shippingweight(approx.):11.4lbs.(5.17kg.).
AL1024ULXPD16CBisamulti-agencyapprovedmulti-outputpowersupply/chargerwhich
convertsa115VAC/60Hzinputintosixteen(16)24VDCClass2Rated
powerlimitedoutputs.
AL1024ULXPD16CB
Multi-Output Power Supply/Charger
Rev.DSAL1024ULXPD16CB_01062012
Overview
AL1024ULXPD16CB
CULListed-CSAStandardC22.2
No.205-M1983,SignalEquipment.

Summary of content (2 pages)