Installation Manual

- 2 - AL1024ULX series
Overview:
The AL1024ULX is a power supply that converts a 115VAC / 60Hz input to a 24VDC regulating output (see speci-
fications below). The AL1024ULX is the base power supply unit for the UL Listed multi-output power supply/
charger series: AL1024ULXPD4, AL1024ULXPD4CB, AL1024ULXPD8, AL1024ULXPD8CB, AL1024ULXPD16,
AL1024ULXPD16CB (Refer to AL1024ULX Series Power Supply Configuration Reference Chart below).
AL1024ULX Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory Power
Distribution
Module(s)
Number of
Output(s)
Class 2 Rated
Power-Limited
Outputs
Fused Outputs
PTC Outputs
Output Rating
(amp) per Output
Power Supply
Output Fuse
Rating
Agency Listings
UL Listings and
File Numbers
AL1024ULX(R)
---- 1 ---- ---- ---- 10
15A/
32V
NFPA 72 Compliant
(Fire-Protective Signaling Service).
UL File # S4707
UL 1481
UL Listed Power
Supplies for Fire
Protective
Signaling Systems.
----------------------------------------
UL 294
UL Listed for
Access Control
System Units.
----------------------------------------
“Signal
Equipment”
Evaluated to
CSA Standard
C22.2
No.205-M1983
AL1024ULXPD4
PD4UL 4 ---- x ----- 3.5
NFPA 72 Compliant
(Fire-Protective Signaling Service).
AL1024ULXPD4CB
PD4ULCB 4 x ---- x 2.5
AL1024ULXPD8
PD8UL 8 ---- x ------ 3.5
AL1024ULXPD8CB
PD8ULCB 8 x ---- x 2.5
AL1024ULXPD16
Two (2)
PD8UL
16 ---- x ---- 3.5
AL1024ULXPD16CB
Two (2)
PD8ULCB
16 x ---- x 2.5
Do not exceed total output rating of 10 amp per unit.
Specifications:
Stand-by Specifications (total current shown):
Output
15 min. of Stand-by &
5 min. of Alarm
4 hr. of Stand-by &
5 min. of Alarm
24 hr. of Stand-by &
5 min. of Alarm
60 hr. of Stand-by &
5 min. of Alarm
24VDC / 12AH
Battery
Stand-By = 8 amp
Alarm = 10 amp
Stand-By = 1.5 amp
Alarm = 10 amp
Stand-By = 200mA
Alarm = 10 amp
Stand-By = 100mA
Alarm = 10 amp
Output
15 min. of Stand-by &
5 min. of Alarm
4 hr. of Stand-by &
5 min. of Alarm
24 hr. of Stand-by &
15 min. of Alarm
60 hr. of Stand-by &
15 min. of Alarm
24VDC / 65AH
Battery
-----------------------------------------------
Stand-By = 8.0 amp
Alarm = 10 amp
Stand-By = 1.5 amp
Alarm = 10 amp
Stand-By = 500mA
Alarm = 10 amp
For Access Control applications, battery capacity for 10 amp supply current - 1 hr. for 24VDC/12AH battery,
6.5 hrs. for 24VDC/65AH battery.
See battery size calculation worksheet for other batteries (Page 7).
Input:
• Input115VAC/60Hz,4.2amp.
• Inputfuserated@5A/250V.
Output:
• 24VDCoutput.
• 8ampsupplycurrentinnon-alarmconditionwith
10 amp supply current during alarm for Fire Alarm
Applications.
10 amp supply current for Access Control Applications.
• Filteredandelectronicallyregulatedoutputs.
• Shortcircuitandthermaloverloadprotection.
BatteryBackup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Automaticswitchovertostand-bybatterywhenACfails.
BatteryBackup(cont’d.):
• Maximumchargecurrent3.6amp.
• Zerovoltagedropwhenswitchedovertobatterybackup.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatterysupervision(form“C”contacts).
• Batterypresencesupervision(form“C”contacts).
LEDIndicators:
• ACinputandDCoutputLEDindicators.
Additional Features:
•Powersupply,enclosure,camlockandbatteryleads
• Allmodelsareavailableinredenclosure
(add an “R” suffix to the part # e.g. AL1024ULXPD8R).
Altronix Corp.
140 58th St. Brooklyn, NY
California
State Fire
Marshal
Factory
Mutual
Approved
LI
S
TED
S
E
C
URITY
SIGNALING
LISTED
LI
S
TED
S
E
C
URITY
SIGNALING
LISTED