Installation Manual

AL1024ULX series - 7 -
Battery size calculation worksheet:
A. AL1024ULX series internal current consumption (stand-by) ______________________ 0.05 A
B. Load current consumption (stand-by) ______________________ A
C. Stand-by time required (hours) ______________________ H
D. Battery capacity required for stand-by (A+B)*C ______________________ AH
E. AL1024ULX series internal power consumption (Alarm) ______________________ 0.05 A
F. Load current consumption (Alarm) ______________________ A
G. Alarm duration (Hours; 15 Min. = 0.25 Hour) (Alarm) ______________________ H
H. Battery capacity required for Alarm (E+F)*G ______________________ AH
I. Totalcalculatedbatterycapacity D+H ______________________ AH
J. Batterycapacityrequired I*1.8(safetyfactor) ______________________ AH
Note:AL1024ULXseriespowersupplyisdesignedtoworkwithbatteriesupto65AH.Pleasenote,line[I]
must not exceeds 36AH. You have to reduce either stand-by current consumption or stand-by time in order to
comply with requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size
(e.g. 3.5 AH = 4.0 AH).