AL300ULX Series Power Supply/Charger Installation Guide Models Include: • AL300ULX - Single Output • AL300ULPD4 - Four (4) Fused Outputs • AL300ULPD4CB - Four (4) PTC Outputs • AL300ULPD8 - Eight (8) Fused Outputs • AL300ULPD8CB - Eight (8) PTC Outputs • AL300ULXPD16 - Sixteen (16) Fused Outputs • AL300ULXPD16CB - Sixteen (16) PTC Outputs For a red enclosure, add an “R” suffix to the part # e.g. AL300ULPD8R Rev.
Overview: The AL300ULX is a power supply that converts a 115VAC / 60Hz input, to a 12VDC or 24VDC regulating output (see specifications below). The AL300ULX is a base power supply unit for the UL Listed multi-output power supply/charger series: AL300ULPD4, AL300ULPD4CB, AL300ULPD8, AL300ULPD8CB, AL300ULXPD16, AL300ULXPD16CB (Refer to AL300ULX Series Power Supply Configuration Reference Chart below).
Power Supply Output Specifications: Output VDC Switch Position Output VDC 12VDC SW1 CLOSED 24VDC Switch Position SW1 OPEN Stand-by Specifications (total current shown): Output 4 hr. of Stand-by & 5 Minutes of Alarm 24 hr. of Stand-by & 5 Minutes of Alarm 60 hr. of Stand-by & 5 Minutes of Alarm 12VDC / 40 AH Battery Stand-by = 2.5 amp Alarm = 2.5 amp Stand-by = 1.0 amp Alarm = 4 amp Stand-by = 300mA Alarm = 4 amp 24VDC / 12 AH Battery Stand-by = 200mA Alarm = 3.
Installation Instructions: The unit should be installed in accordance with article 760 of The National Electrical Code as well as NFPA 72 and all applicable Local Codes. 1. Mount the unit in desired location. 2. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1B, pg. 3) to the appropriate position (Power Supply Voltage Output Selections Chart, pg. 3). 3. Secure cabinet to earth gournd. Connect AC power (115VAC / 60 Hz to terminals marked [L, G, N] (Fig. 1, pg. 3).
LED Diagnostics: PD4UL/PD4ULCB/PD8UL/PD8ULCB - Power Distribution Module Green Power Distribution Module Status ON Normal operating condition. Terminal Identification: PD4UL/PD4ULCB/PD8UL/PD8ULCB - Power Distribution Module Terminal Legend PD4UL/PD4ULCB PD8UL/PD8ULCB Function/ Description 1P to 4P 1P to 8P Positive DC power outputs. 1N to 4N 1N to 8N Negative DC power outputs. Power Distribution Module(s): Fig. 2B Fig. 2A Replace fuses with the same type and rating 3.5A, 250V.
Wiring: USE 14 AWG or larger for all power connections. Note: Take care to keep power limited circuits separate from non-power limited wiring (115VAC, Battery). Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (Power Supply Voltage Output Specifications Chart, pg. 3).
Enclosure Dimensions: • AL300ULXPD16 • AL300ULXPD16CB 15.5”H x 12”W x 4.5”D 12" 2.25" 4.56" 3.68" 1.22" 4.5" 1.22" .875" 1.22" 1.3" 9.97" 1" 1" 2" 2" 8" 13.25" 13.53" 3.25" 2.2" 1.25" 1" 15.5" 1.22" 2.25" 3.68" 4.
Notes: Altronix is not responsible for any typographical errors. Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.