Spec Sheet
- 6 -
Wiring:
USE 14 AWG or larger for all power connections.
Note: Take care to keep power limited circuits separate from non-power limited wiring (115VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Power Supply Voltage Output Specifications Chart, pg. 3).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at
battery terminal and at the board terminals marked [- BAT +] to insure there is no break in the battery connection
wires.
Note: Maximum charging current under discharges is .7 amp.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
Enclosure Dimensions:
• AL300ULX
• AL300ULPD4
• AL300ULPD4CB
• AL300ULPD8
• AL300ULPD8CB
13”H x 13.5”W x 3.25”D
00
0
.81"
0
1.1875"
1.1875"
3.25"
3.25"
0 1.1875" 3.25".75" 1.5" 6.25" 11"
1.4"
6.5"
5.5"
1.4"
11.66"
12.1"
13"
12.5"
11.75"
TOP ONLY