M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: • AL300ULM - 2.5 amp @ 12VDC or 24VDC. • AL400ULM - 4 amp @ 12VDC or 3 amp @ 24VDC. • AL600ULM - 6 amp @ 12VDC or 24VDC. • AL1012ULM - 10 amp @ 12VDC. • AL1024ULM - 10 amp @ 24VDC. For a red enclosure, add an “R” suffix to the part # e.g. AL300ULMR Rev.
Overview: These multi-output access control power supply/charger is specifically designed for use with access control systems and accessories. These units convert a 115VAC / 60Hz input into five (5) individually protected 12VDC or 24VDC outputs (see specifications). Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes.
Specifications (cont’d): Visual Indicators: Supervision (cont’d): • DC output LED indicator. • LEDs indicate condition of power outputs. • Power & input trigger LED’s. • Battery presence supervision (form “C” contact). • Power fail supervision relay (form “C” contact rated 1 amp @ 28VDC). • Power supply is complete with enclosure, cam lock, transformer and battery leads. Supervision: • AC fail supervision (form "C" contact). • Low battery supervision (form "C" contact).
Output Voltage and Stand-by Specification Charts: AL300ULM Output Switch Position 12VDC / 40 AH Battery Closed 24VDC / 12 AH Battery Open 24VDC / 40 AH Battery Open 4 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 2.5 amp Alarm = 2.5 amp Stand-by = 2.5 amp Alarm = 2.5 amp 24 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 1.0 amp Alarm = 2.5 amp Stand-by = 200mA Alarm = 2.5 amp Stand-by = 1.0 amp Alarm = 2.5 amp 60 hr. of Stand-by & 5 Minutes of Alarm Stand-by = 300mA Alarm = 2.
Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (Output Voltage and Stand-by Specification Charts, pg. 3 & 4).
LED Diagnostics: Power Supply Board Red (DC) LED Green (AC) Power Supply Status ON ON Normal operating condition. ON OFF Loss of AC, Stand-by battery supplying power. OFF ON No DC output. Short circuit or thermal overload condition. OFF OFF No DC output. Loss of AC. Discharged battery. MOM5 - Output Module LED Power (Green) Trigger (Green) Outputs (Red) ON Normal operation. Input is triggered (alarm condition). Output tripped due to a short circuit or overload condition.
Terminal Identification Tables: Power Supply Board Terminal Legend Function/Description L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground. - DC + AL300ULM - 12VDC/24VDC @ 2.5 amp to MOM5 board (power limited). AL400ULM - 12VDC @ 4 amp or 24VDC @ 3 amp to MOM5 board (power limited). AL600ULM - 12VDC/24VDC @ 6 amp to MOM5 board (non-power limited). AL1012ULM - 12VDC @ 10 amp to MOM5 board (non-power limited). AL1024ULM - 24VDC @ 10 amp to MOM5 board (non-power limited).
Typical Application Diagrams: Fig. 2 MOM5 module shown with wet and/or dry nor- (+) (-) MOM5 module shown with wet and/or dry normally open trigger inputs (Non-Latching): DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE NEG (-) INPUT POS (+) NEG (-) INPUT POS (+) mally closed trigger inputs (Non-Latching): (+) (-) DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE N.C. INPUT FROM FACP OR ACCESS CONTROL DEVICE EOL 2.2K TRIGGER TRIGGER EOL 2.2K N.O.
Typical Application Diagrams (cont’d.): MOM5 module shown with with wet and/or dry normally closed fire alarm trigger inputs (Latching with Manual Reset): MOM5 module shown with with wet and/or dry normally open fire alarm trigger inputs (Latching with Manual Reset): (+) (-) DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT NEG (-) INPUT POS (+) NEG (-) INPUT POS (+) Fig. 5 (-) DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT TRIGGER TRIGGER EOL 2.2K (+) N.O.
Enclosure Dimensions: • AL300ULM • AL400ULM • AL600ULM 13”H x 13.5”W x 3.25”D 3.25" TOP ONLY 1.1875" 0 3.25" 1.1875" 0 0 .75" 1.5" 6.25" 11" 11.75" 12.5" 0 0 .81" 1.4" 1.4" 5.5" 6.5" 11.66" 12.1" 13" - 10 - 1.1875" 3.
Enclosure Dimensions: • AL1012ULM • AL1024ULM 15.5”H x 12”W x 4.5”D 4.5" TOP & BOTTOM 1.25" 0 1.5" 4.5" 1.25" 0 6" 0 .875" 10.5" 10.75" 12" 0 0 1" 2" 6.625" 10" 13.5" 14.25" 15.5" - 11 - 1.25" 4.
Notes: Altronix is not responsible for any typographical errors. Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.