Spec Sheet

Overview:
These multi-output access control po
wer supply/charger is specifically designed for use with access control systems and
accessories.
These units convert a 115VAC / 60Hz input into five (5) individually protected 12VDC or 24VDC outputs (see
specif
ications). Each output will route power to a variety of access control hardware devices including Mag Locks, Electric
Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trig-
ger input is achieved through normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal from
an FACP (Fire Alarm Control Panel). A form “C” dry output relay enables HVAC Shutdown, Elevator Recall or may be
used to trigger auxiliary devices.
- 2 -
Input:
Power input 115VAC 60Hz (see reference chart above).
Fire Alarm Panel or Access Control System trigger
inputs. N.O. or N.C. supervised trigger input and
polarity reversal trigger input (4mA draw from FACP).
Output:
Five (5) individual power limited class 2 rated outputs.
Cur
rent limit is 2.5 amp @ 12VDC or 24VDC
per output (12VDC onl
y for
AL1012ULM and
24VDC only for AL1024ULM).
Filtered and electronically regulated outputs.
Thermal and short circuit protection with auto reset.
Overload protection.
Output relay energizes when unit is triggered
(form “C” contact rated 1 amp @ 28VDC).
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when AC fails.
AL300ULXB, AL400ULXB, AL600ULXB and
AL1012ULXB (Power Supply Board) maximum
charge current .7 amp.
AL1024ULXB (P
ower Supply Board) maximum charge
cur
rent 3.6 amp).
• Zero v
oltage drop w
hen s
witching o
ver to
batter
y backup.
AL300ULM, AL400ULM and AL600ULM enclosure
accommodates up to two (2) 12VDC/7AH batteries.
AL1012ULM and
AL1024ULM enclosure
accommodates up to two (2) 12VDC/12AH batteries.
AL300ULM 2.5 2.5 5 Yes 1.45
AL400ULM 4 3 5 Yes 1.9
AL600ULM 6 6 5 Yes 2.5
AL1024ULM - 10 5 Yes 4.4
AL1012ULM 10
- 5 Yes 1.9
UL File # S4707
UL 1481
UL Listed Power Supply for
Fire Protective Signaling Systems
UL 294
UL Listed Access Control System Unit.
UL 603
UL Listed for Burglar Alarms Systems.
UL 1069
UL Listed Hospital Signaling and Nurse Call Equipment.
“Signal Equipment” Evaluated to CSA 22.2
N205-M1983
M Series Power Supply Configuration Reference Chart:
Altronix
Model Number
California
State
Fire Marshal
NYC Dept.
of Buildings
115VAC 60Hz Input
(current dra
w/amp)
12VDC Total Output
Current (amp)
24VDC Total Output
Current (amp)
Outputs
Class 2 Rated
Power Limited
Agency Lisitings
UL Listings and
File Numbers
Power Suppl
y Board
Input Fuse Rating
Specifications:
3.5 amp
250VAC
3.5 amp
250VAC
3.5 amp
250VAC
3.5 amp
250VAC
10 amp
250VAC
UL File # S4707
UL 1481
UL Listed Power Supply for
Fire Protective Signaling Systems
UL 294
UL Listed Access Control System Unit.
“Signal Equipment” Evaluated to CSA 22.2
N205-M1983
UL File # S4707
UL 1481
UL Listed Power Supply for
Fire Protective Signaling Systems
UL 294
UL Listed Access Control System Unit.
“Signal Equipment” Evaluated to CSA 22.2
N205-M1983
UL File # BP617
UL 294
UL Listed Access Control System Unit.
“Signal Equipment” Evaluated to CSA 22.2
N205-M1983