Spec Sheet
Output Voltage and Stand-by Specification Charts:
AL300ULM
Output Switch 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by &
Position 5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm
12VDC / 40 AH Battery Stand-by = 2.5 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 2.5 amp Alarm = 2.5 amp Alarm = 2.5 amp
24VDC / 12 AH Battery Stand-by = 200mA
Alarm = 2.5 amp
24VDC / 40 AH Battery Stand-by = 2.5 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 2.5 amp Alarm = 2.5 amp Alarm = 2.5 amp
AL400ULM
Output Switch 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by &
Position 5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm
12VDC / 40 AH Battery Stand-by = 4.0 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 4.0 amp Alarm = 4.0 amp Alarm = 4.0 amp
24VDC / 12 AH Battery Stand-by = 200mA
Alarm = 3.0 amp
24VDC / 40 AH Battery Stand-by = 3.0 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 3.0 amp Alarm = 3.0 amp Alarm = 3.0 amp
AL600ULM
Output Switch 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by &
Position 5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm
12VDC / 40 AH Battery Stand-by = 6.0 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 6.0 amp Alarm = 6.0 amp Alarm = 6.0 amp
24VDC / 12 AH Battery Stand-by = 200mA
Alarm = 6.0 amp
24VDC / 40 AH Battery Stand-by = 6.0 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 6.0 amp Alarm = 6.0 amp Alarm = 6.0 amp
AL1012ULM
Output
15 Minutes of Stand-by @ 10 amp
12VDC / 12 AH Battery
AL1024ULM
Output 15 mins. Stand-by / 4 hr. Stand-by / 24 hr. Stand-by / 60 hr. Stand-by /
5 mins. Alarm 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm
2 4 V D C / 1 2 A H B a t t e r y 7 . 7 a m p / 9 . 7 a m p 1 . 2 a m p / 9 . 7 a m p ------------------------- -------------------------
24VDC / 65 AH Battery ------------------------- 7.7 amp / 9.7 amp 1.2 amp / 9.7 amp 200mA / 9.7 amp
- 4 -
ClosedClosed
Open
Open
ClosedClosed
Open
Open
ClosedClosed
Open
Open