Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Output Voltage and Stand-by Specification Charts, pg. 3 & 4).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at
the battery terminals and at the board terminals marked [+ BAT-- ] to insure that there is no break in the battery
connection wires.
Note: AL300ULXB, AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge
current is .7 amp.
AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp.
Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.
- 5 -
--- D C
+
L G N
NC C NO NC C NO
+
BAT ---
AC FAIL
BAT FAIL
Door
Battery 1
Battery 2
Green
Lead
Battery connection (non power limited)
Wir
e
Strap
(from
Enclosure
to Door)
115VAC
power mains
non-power
limited
Class 1
Divider
NC C NO
DRY OUTPUT
TRIGGER
LED
6 7 8 9 10
POS (+) DC OUTPUT (STANDBY)
NC C NO
POWER FAI L
TRIGGER
1 2 3 4 5
POS (+) DC OUTPUT (ALARM)
NEG1 NEG2 NEG3 NEG4 NEG5
-- DC INPUT +
NEG (-) INPUT POS (+)
DC Output to devices
(power limited)
Fire Alarm
Interface
non-power limited
Power Supply Board
CAUTION: De-energize unit prior to servicing. For continued protection
against risk of electric shock and fire hazard replace fuses with the same type
and rating (see marking on the board). Replace fuse cover before energizing.
Do not expose to rain or moisture.
Keep power limited wiring separate from non-power limited.
Use minimum .25" spacing.
Fuse
Cover
Power Limited
NC C NO NC C NO
AC FAIL
BAT FAIL
Battery & AC
Supervision Circuit
(power limited)
Fig. 1
Fig. 1A