Data Sheet
Input:
• Input 115VAC / 60Hz, 3.5 amp.
• Input fuse rated @ 5 amp/250V.
• Fire Alarm Panel or Access Control System trigger
inputs. N.O. or N.C. supervised trigger input and
polarity reversal trigger input.
Output:
• 12VDC or 24VDC selectable outputs.
• 12VDC @ 4 amp or 24VDC @ 3 amp supply current.
• Burglar Alarm Applications:
12VDC = 10VDC-13.2VDC;
24VDC = 20VDC-26.4VDC.
• Five (5) PTC protected Class 2 Rated power-limited
outputs, rated @ 2 amp.
• Output relay energizes when unit is triggered
(form “C” contact rated 1 amp @ 28VDC).
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7 amp.
Supervision:
• AC fail supervision (form “C” contacts).
- Notification trigger is selectable for
30 seconds (factory set) or 6 hours.
• Low battery supervision (form “C” contacts).
• Battery presence supervision (form “C” contacts).
• Power fail supervision relay (form “C” contacts).
Visual Indicators:
• AC input and DC output LED indicators
(power supply board).
• Red LEDs indicate condition of power outputs
(multi-output board).
• Power and input trigger LEDs (multi-output board).
Electrical:
• Operating temperature: 0º C to 49º C ambient.
• BTU/Hr.:
- 12VDC: 24.57 BTU/Hr.
- 24VDC: 36.85 BTU/Hr.
• System AC input VA requirement: 402.5VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
- Accommodates up to two (2) 12VDC/7AH batteries.
• Product weight (approx.): 7.6 lbs. (3.45 kg).
• Shipping weight (approx.): 8.6 lbs. (3.9 kg).
Specifications
AL400ULMR
Multi-Output Power Supply/Charger
Rev. DSAL400ULMR_05212015
AL400ULMR multi-output access control power supply/charger is specifically
designed for use with access control systems and accessories. This unit con-
verts a 115VAC / 60Hz input into five (5) individually protected Class 2 Rated
power-limited 12VDC or 24VDC outputs. Each output will route power to a va-
riety of access control hardware devices including Mag Locks, Electric Strikes,
Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and
Fail-Secure modes. Controlled trigger input is achieved through normally open
(N.O.) or normally closed (N.C.) supervised input or the polarity reversal from
an FACP (Fire Alarm Control Panel). A form “C” dry output relay enables
HVAC Shutdown, Elevator Recall or it may be used to trigger auxiliary devices.
Overview
AL400ULMR
Agency Approvals
Altronix Corp.
140 58th St. Brooklyn, NY
UL Listed for Access Control Systems Units
(UL 294).
UL Listed Standard for Power Supplies for Use
with Burglar-Alarm System Units (UL 603).
UL Listed Hospital Signaling and Nurse Call
Equipment (UL 1069).
UL Listed Standard for Safety for Fire
Protective Signaling Systems (UL 1481).
CUL Listed - CSA Standard C22.2
No.205-M1983 Signal Equipment.
CSFM - California State Fire
Marshal Approved.
MEA - NYC Department of
Buildings Approved.