Spec Sheet

Overview:
The AL400ULX is a power supply that converts a 115VAC / 60Hz input, to a 12VDC or 24VDC regulating output,
(see specifications below).
The AL400ULX is the base power supply unit for the UL Listed multi-output power supply/charger series:
AL400ULPD4, AL400ULPD4CB, AL400ULPD8, AL400ULPD8CB, AL400ULXPD16, AL400ULXPD16CB
(Refer to AL400ULX Series Power Supply Configuration Reference Chart below).
AL400ULX(R) -
1-- 4 3
AL400ULPD4 PD4UL 4 x - 3.5 3
AL400ULPD4CB PD4ULCB 4 - x 2.5 2.5
AL400ULPD8 PD8UL 8 x - 3.5 3
AL400ULPD8CB PD8ULCB 8 - x 2.5 2.5
AL400ULXPD16 16 x - 3.5 3
AL400ULXPD16CB 16
-
x
2.5
2.5
Do not exceed total output rating of 4 amp @ 12VDC or 3 amp @ 24VDC per unit.
UL File # S4707
UL 294
UL Listed for Access Control System Units.
UL 603
UL Listed Standard for Power Supplies for Use
with Burglar-Alarm Systems.
UL 1069
UL Listed Hospital Signaling and
Nurse Call Equipment.
UL 1481
UL Listed Standard for Safety for
Fire Protective Signaling Systems.
“Signal Equipment” Evaluated to
CSA Standard C22.2
No.205-M1983
AL400ULX Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory P
ower
Distribution
Module(s)
Number of Outputs
Fused Outputs
PTC Outputs
Agency Lisitings
UL Listings and
File Numbers
- 2 -
12VDC Per Output
Current (amp)
24VDC P
er Output
Current (amp)
Input:
Input 115VAC / 60Hz, 1.45 amp.
AC input and DC output LED indicators.
Output:
Class 2 Rated power limited output(s).
12VDC or 24VDC selectable output.
4 amp total supply current at 12VDC
or 3 amp total supply current at 24VDC.
Filtered and electronically regulated outputs.
Short circuit and thermal overload protection.
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Battery Backup (cont’d.):
Automatic switch over to stand-by battery when
AC fails.
Maximum char
ge current .7 amp.
Zero voltage drop when switched over to battery backup.
Supervision:
AC fail supervision (form "C" contacts).
Low battery supervision (form "C" contacts).
Battery presence supervision (form “C” contacts).
Additional Features:
Power supply, enclosure, cam lock and battery leads.
All models are available in red enclosure
(add an “R” suf
fix to the part # e.g.
AL400ULPD8R).