Installation Guide

eBridge4SK - 5 -
4. HTTP Port: Enter the HTTP port number assigned to the eBridge4SPT module by the network administrator to allow remote access and monitoring.
The default inbound port setting is 80. HTTP is not encrypted and unsecure. Even though HTTP can be used for remote access it is recommended primarily
for use with LAN connections.
5. HTTPS Port: Enter the HTTPS port number assigned to the eBridge4SPT module by the network administrator to allow remote access and monitoring.
The default inbound port setting is 443. Being encrypted and more secure, HTTPS is highly recommended for remote access.
6. Click the button labeled Submit Network Settings. A dialog box will display “New network settings will take effect after the server is rebooted”. Click OK.
Trap Receiver Settings (Fig. 2b, pg. 4):
1. Enter up to five SNMP trap receiver IP addresses. When accessing the eBridge4SPT remotely check with the network administrator for proper configuration.
2. Click the button labeled Submit Trap Receiver IP Settings. A dialog box will display “New Trap Receiver IP settings will take effect after the
server is rebooted”. Click OK.
SNMP Port Settings (Fig. 2c, pg. 4):
SNMP uses the default port 161 for general SNMP messages and port 162 for SNMP trap messages. In the event these port need to be changed enter the new port
numbers assigned by the network administrator. Click the button labeled Submit Port Settings. A dialog box will display “New SNMP port settings will take
effect after the server is rebooted”. Click OK.
Email Settings (Fig. 2d, pg. 4):
The eBridge4SPT can send emails via an in-house email server, email service provider (i.e. Gmail, Yahoo) or Altronix default email service.
In-house email server:
1. From: Enter the email address assigned to the eBridge4SPT module by the system administrator.
2. Subject: Identify the location of the ebridge4SPT (i.e. the Site ID).
3. Username: Enter the username associated with the eBridge4SPT module email address.
4. Password: Enter the username password.
5. SMTP server IP: Enter the SMPT IP address of the in-house email server.
6. SMTP server Port: Enter the SMPT port assigned to the in-house email server.
7. Outgoing Email Address 1-5: Enter up to five outgoing email addresses.
8. Click the button labeled Submit Email Settings email setting will be saved.
Email service provider:
1. From: Enter the email address for the eBridge4SPT module.
2. Subject: Identify the location of the eBridge4SPT (i.e. the Site ID)
3. Username: Enter the username associated with the eBridge4SPT module email address.
4. Password: Enter the username password
5. SMTP server IP: Enter the SMPT IP address of the email service provider.
6. SMTP server Port: Enter the email SMPT port number. The default SMPT email ports are 25 or 465 unless otherwise specified.
7. Outgoing Email Address 1-5: Enter up to five outgoing email addresses.
8. Click the button labeled Submit Email Settings email setting will be saved.
Altronix default email service:
1. All required sender and network fields have already been populated.
2. Outgoing Email Address 1-5: Enter up to five outgoing email addresses.
3. Click the button labeled Submit Email Settings. Email settings will be saved.
To test the email setup click the button labeled Test Email. An email will be sent to all Outgoing email addresses. If the test email is not received contact the