eFlow102N Series Power Supply/Chargers Models Include: eFlow102N/ eFlow102NX - 10A @ 12VDC eFlow102N8/ eFlow102NX8 eFlow102N8D/ eFlow102NX8D - 10A @ 12VDC - Eight (8) Fused Outputs - 10A @ 12VDC - Eight (8) PTC Protected Class 2 Power-Limited Outputs eFlow102N16/ eFlow102NX16 eFlow102N16D/ eFlow102NX16D - 10A @ 12VDC - Sixteen (16) Fused Outputs - 10A @ 12VDC - Sixteen (16) PTC Protected Class 2 Power-Limited Outputs Installation Guide Altronix Corp. 140 58th St. Brooklyn, NY Rev.
Overview: Altronix eFlow102N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC nominal output (see Power Supply Configuration Reference Chart and Specifications). 10.03- 10.0310A 13.2 13.2 3.5A 5A/ 15A/ 760 250V 32V PD8UL 8 9.7813.2 10.0310A 13.2 3.5A 5A/ 15A/ 760 250V 32V PD8ULCB 8 10.03- 10.0310A 13.2 13.2 3.5A 5A/ 15A/ 760 250V 32V 9.78- 10.03-1 10A 13.2 3.2 3.
Stand-by Specifications: Battery 7AH 12AH 40AH (for eFlow102NX refer to Fig. 8, pg. 10) 65AH (for eFlow102NX refer to Fig. 8, pg. 10) Burg. Applications 4 hr. Stand-by/ 15 min. Alarm 0.4A/10A 1A/10A 6A/10A 6A/10A Fire Applications 24 hr. Stand-by/ 5 min. Alarm N/A 0.3A/10A 1.2A/10A 1.5A/10A Access Control Applications Stand-by 5 Mins./10A 15 Mins./10A Over 2 Hours/10A Over 4 Hours/10A Specifications: Input: Supervision: • 120VAC, 60Hz. • Low power shutdown.
3. Measure output voltage before connecting devices. This helps avoiding potential damage. 4. Connect devices to be powered: a. For eFlow102N/eFlow102NX connect devices to terminals marked [– DC +] (Fig. 1h, pg. 5). b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 6) or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4a & 4b, pg. 6) carefully observing correct polarity.
Terminal Identification: Power Supply/Charger Terminal Legend L, N – DC + Trigger EOL Supervised NO, GND RESET + AUX – AC Fail NC, C, NO Bat Fail NC, C, NO – BAT + Function/Description Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited) (Fig. 1a, pg. 5). 12VDC nominal @ 10A continuous output (non power-limited output) (Fig. 1h, pg. 5). Fire Alarm Interface trigger input from a short or FACP.
Fig. 2 - Battery Trouble Indication For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure. Wire one leg of a UL Listed, power-limited power source to the indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked [BAT FAIL - C, NO] (Fig. 2, pg. 6).
Fig. 5 - eFlow102N Configuration Enclosure Edge of Enclosure Tamper Switch (included) To Access Control Panel or UL Listed Reporting Device Green Lead L G 120VAC power mains non power-limited PD8UL/PD8ULCB N PD16W/ PD16WCB AC1 AC FAIL BAT FAIL NC C NO NC C NO Battery & AC Supervision Circuit (power-limited) DC Output to Devices* (refer to Fig. 3a, 3b, 4a, 4b for board configuration, pg.
NEC Power-Limited Wiring Requirements for eFlow102N Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Fig. 7 - eFlow102NX Configuration Enclosure Edge of Enclosure Tamper Switch (included) To Access Control Panel or UL Listed Reporting Device Battery & AC Supervision Circuit (power-limited) AC1 L G N NC C NO NC C NO AC FAIL BAT FAIL Battery Connection non power-limited - BAT + - DC + Green Lead AC DC TRIGGER EOL SUPERVISED NO GND +AUX- RESET power-limited 120VAC power mains non power-limited PD8UL/PD8ULCB PD8UL/PD8ULCB DC Output to Devices* (refer to Fig.
NEC Power-Limited Wiring Requirements for eFlow102NX Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below.
Enclosure Dimensions (BC300): eFlow102N, eFlow102N8, eFlow102N8D, eFlow102N16, eFlow102N16D 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm) 1.40” (35.6mm) 4.85” (123.2mm) 4.85” (123.2mm) 1.40” (35.6mm) 1.20” (30.5mm) 0.75” (19.1mm) 3.25” (82.6mm) 1.20” (30.5mm) 0.75” (19.1mm) 12.5” (317.5mm) 11.0” (279.4mm) 1.20” (30.5mm) 0.9375” (23.8mm) 1.40” (35.6mm) 1.40” (35.6mm) 5.10” (129.5mm) 5.10” (129.5mm) 13.0” (330.2mm) 6.5625” (166.7mm) 5.10” (129.5mm) 0.9375” (23.8mm) 3.25” (82.6mm) 3.
Enclosure Dimensions (BC400): eFlow102NX, eFlow102NX8, eFlow102NX8D, eFlow102NX16, eFlow102NX16D 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm) 1.5” (38.1mm) 4.615” (117.2mm) 4.615” (117.2mm) 1.5” (38.1mm) 1.75” (44.5mm) 1.25” (31.8mm) 4.5” (114.3mm) 4.5” (114.3mm) 12.23” (310.6mm) 1.1” (27.9mm) 1.1” (27.9mm) 1.375” (34.9mm) 1.5” (38.1mm) 1.25” (31.8mm) 1.5” (38.1mm) 0.91” (23.1mm) 0.91” (23.1mm) 1.125” (28.6mm) 15.5” (393.7mm) 2.0” (50.8mm) 2.0” (50.8mm) 5.0” (127.0mm) 0.79” (20.
Appendix A - UL Listed Compatible Devices –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with eFlow102N output.
eFlow Power Supply/Chargers can be Controlled and Monitored while Reporting Power/Diagnostics from Anywhere over the Network... LINQ2 - Network Communication Module LINQ2 provides remote IP access to real-time data from eFlow power supply/chargers to help keep systems up and running at optimal levels.
Notes: Altronix is not responsible for any typographical errors. –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.
Power Supply/Chargers Operating Guide Models Include: Model eFlow102N, eFlow102N8, eFlow102N8D, eFlow102N16, eFlow102N16D eFlow102NX, eFlow102NX8, Flow102NX8D, eFlow102NX16, eFlow102NX16D Output Input 120VAC, 60Hz 12VDC 24VDC 3.5A 10A – Auxiliary Power-Limited Ripple Output (unswitched) Voltage 1A 760mV Overview: The eFlow102N series power supply/chargers convert a 120VAC, 60Hz input to a 12VDC output. Stand-by Specifications: Battery 7AH 12AH 40AH 65AH Fire Applications 24 hr.