Data Sheet
eFlow6NA8 distributes and switches power to access control systems and accessories.
It converts a 120VAC 60Hz input into eight (8) independently controlled 12VDC or
24VDC fuse protected outputs with a total of 6 amp continuos supply current. These
power outputs can be converted to dry form “C” contacts. Outputs are activated by an
open collector sink or normally open (NO) dry trigger input from an Access Control
System, Card Reader, Keypad, Push Button, PIR, etc. Unit will route power to a
variety of access control hardware devices including: Mag Locks, Electric Strikes,
Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure
modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be
used to trigger other auxiliary devices. The fire alarm disconnect feature is individu-
ally selectable for any or all of the eight (8) outputs.
eFlow6NA8
Power Supply/Charger with Multi-Output
Access Power Controllers
Rev. DSeFlow6NA8_02182014
Overview
Specifications
Input:
• Input120VAC60Hz,3.5amp.
• Powersupplyinputoptions:
a) One (1) common power input for ACM8 and lock
power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8 and one (1) for lock accessory power,
(external power supply is required). Current is
determined by the power supply connected, not to
exceed a maximum of 10 amp total.
• Eight(8)AccessControlSystemtriggerinputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
Output:
• 12VDCor24VDCoutputs@6ampsupplycurrent.
• Eight(8)independentlytriggercontrolledoutputs.
Output options:
a) Eight (8) Fail-Safe filtered power outputs.
b) Eight (8) Fail-Secure filtered power outputs.
c)Eight(8)form“C”relayoutputs(rated@5amp/
24VDC or VAC).
d) Any combination of the above.
• Eight(8)unswitchedfilteredaux.poweroutputs
(outputsarerated@2.5amp).
• OverVoltageprotection.
• Shortcircuitandthermaloverloadprotection.
Fire Alarm Disconnect:
• FireAlarmdisconnect(latchingornon-latching)is
individually selectable for any or all of the
eight (8) outputs.
• FireAlarmdisconnectinputoptions:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b) Polarity reversal input from FACP signaling circuit.
• AlarmoutputrelayindicatesthatFACPinputis
triggered(form“C”contactrated@1amp28VDC
not evaluated by UL).
Supervision:
• ACfailsupervision(form“C”contacts).
• Batteryfail&presencesupervision
(form “C” contacts).
• Lowpowershutdown.ShutsdownDCoutput
terminalsifbatteryvoltagedropsbelow71-73%for
12Vunitsand70-75%for24Vunits(dependingon
the power supply). Prevents deep battery discharge.
Visual Indicators:
ACM8 Access Power Controller:
• RedLEDsindicateoutputsaretriggered
(relays energized).
• GreenLEDindicatesFACPdisconnectistriggered.
eFlow Power Supply Board:
• ACinputandDCoutputLEDindicators.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• PowerSupplyBoardmaximumchargecurrent
1.54amp.
• Automaticswitchovertostand-bybatterywhenAC
fails. Transfer to stand-by battery power is
instantaneous with no interruption.
• Zerovoltagedropwhenunitswitchesovertobattery
backup (AC failure condition).
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• ACM8boardmainfuseisratedat10amp.
• BTU/Hr.:
- 12VDC:36.85BTU/Hr.
- 24VDC:73.7BTU/Hr.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm)
- Combinationknockoutsare0.625”and0.75”.
- Accommodates up to two (2) 12AH batteries.
• Productweight(approx.):8.6lbs.(3.9kg).
• Shippingweight(approx.):9.9lbs.(4.49kg).
eFlow6NA8