Spec Sheet

Input
Voltage 120VAC, 60Hz.
Fusing Varies, see Reference Chart.
Outputs
Voltage 12VDC or 24VDC, see Reference Chart.
Current Varies, see Reference Chart.
Auxiliary Class 2 power-limited @ 1A (unswitched).
Other Overvoltage protection.
Filtered and regulated.
Back-up Battery (not included)
Capacity 12AH / 12VDC (Up to 4 within enclosure).
40 AH / 65 AH (requires separate enclosure).
Type Sealed lead acid or gel type.
Fuse Rating Varies, see Reference Chart.
Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non latching.
EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below
71-73% for 12V units and 70-75% for 24V units
(depending on the power supply). Prevents deep battery discharge.
Indicators (LED)
Input 120VAC is present.
DC Output Powered.
Physical and Environmental
Dimensions (H x W x D)
20.5” x 16.5” x 6.25” (520.7mm x 419.1mm x 158.8mm).
Weight (approx.):
Model Product Weight Shipping Weight
MaxFit11FE 21.2 lb. (9.6 kg) 26.6 lb. (12.1 kg)
MaxFit13FE 21.2 lb. (9.6 kg) 26.6 lb. (12.1 kg)
MaxFit33FE 21.2 lb. (9.6 kg) 26.6 lb. (12.1 kg)
MaxFit35FE 21.2 lb. (9.6 kg) 26.6 lb. (12.1 kg)
MaxFit37FE 21.2 lb. (9.6 kg) 26.6 lb. (12.1 kg)
MaxFit55FE 21.2 lb. (9.6 kg) 26.6 lb. (12.1 kg)
MaxFit75FE 21.2 lb. (9.6 kg) 26.6 lb. (12.1 kg)
MaxFit77FE 21.7 lb. (9.8 kg) 27.1 lb. (12.3 kg)
Temperature
Operating 0ºC to 49ºC (32ºF to 120ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr (approx.):
Model 12VDC 24VDC 12 and 24VDC
MaxFit11FE 48 74 98
MaxFit13FE 61 123 98 or 86*
MaxFit33FE 74 148 111
MaxFit35FE 98 N/A 130
MaxFit37FE N/A 197 160
MaxFit55FE 123 N/A N/A
MaxFit75FE N/A N/A 184
MaxFit77FE N/A 246 N/A
*Depending on Power Supplies’ settings
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com
Specifications
Accessories
Network Supervision
Altronix model LINQ2 Network Communication Module provides remote supervision,
control and monitoring over LAN/WAN
- Remotely reports accurate power diagnostics
- Controls power and resets devices
- Reports system diagnostics via Email
MaxFit FE Series
Dual P/S Expandable Power Systems